Plan Review Notes
Plan Review Notes For Permit 07080952
Permit Number 07080952
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-10 15:39:26 
  
 APPLICATION #07080952
 ELECTRICAL PLAN REVIEW
 310 FLAMINGO DRIVE
 12/10/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 ALTHOUGH THE ELECTRICAL REVIEW WAS PASSED ON 9/12/07,
 THESE COMMENTS COME FROM NEW INFORMATION AND DRAWINGS
 SUBMITTED ON 11/28/07.
  
 1} ELECTRICAL SPECIFICATIONS, SHEET E-0, PART 3 (A),
 INDICATES THE COLOR CODING FOR A SINGLE PHASE, 120/240
 VOLT SYSTEM. THE RISER DIAGRAM INDICATES THE SERVICE
 BEING 3 PHASE 120/208 SYSTEM, CORRELATE SAME.
  
 2} THE PANEL SCHEDULES INDICATE THE PANELS ARE ?FED
 FROM UTILITY?, CORRECT TO INDICATE FED FROM MAIN
 DISCONNECT.106.1.3 FBC AS AMENDED.
  
 3} INDICATE THE BRANCH CIRCUIT CONDUCTOR SIZES ON THE
 PANEL SCHEDULE SO THAT COMPLIANCE WITH 310.16 CAN BE
 REVIEWED.
  
 4} CIRCUIT LPA-5 HAS TWO RECEPTACLES LOCATED ON A
 KITCHEN COUNTERTOP AND MUST COMPLY WITH SMALL APPLIANCE
 BRANCH CIRCUIT ARTICLES. SEE 210.52(A), 210.52(C), AND
 210.8(A)(6) GFI.
  
 5} SEE 210.52(C)(2) FOR ISLAND RECEPTACLE REQUIREMENT,
 LOCATE SAME ON PLAN.
  
 6} THE MOCP FOR AIR HANDLERS 1,2 AND 4, ON SHEET M.2,
 AND THE OCP IN THE PANEL SCHEDULES, SHEET E-0, FOR
 THOSE UNITS ARE IN CONFLICT. CORRELATE SAME.
  
 7}210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING. LOCATE SAME ON PLANS.
  
 8} CIRCUIT LPA-35 AND LPA-17 MUST BE AFCI PROTECTED PER
 210.12.
  
 9} THE ENERGY CERTIFICATIONS SUBMITTED ARE FOR A
 WAREHOUSE, SHEET A.1 INDICATES AN R3 BUILDING TYPE. THE
 APPLICATION STATES NO CHANGE OF OCCUPANCY. THE GARAGE
 IS LABELED ?ACCESSORY TO RESIDENCE?.CORRELATE THESE
 DOCUMENTS, DECLARE OCCUPANCY TYPE, IF R3 CHECK THE
 CHANGE OF OCCUPANCY BOX ON THE APPLICATION, SUBMIT
 ENERGY CALCULATIONS PER 13-600.
  
 THE ELECTRICAL REVIEW WAS DONE FOR R3 AS INDICATED ON
 THE PLAN. PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND
 REPLACE WITH CORRECTED ONES WHEN RESUBMITTING. INCLUDE
 THEM SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND
 TO REVIEW COMMENTS IN WRITING.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  