| 2007-12-10 15:39:26 | |
| | |
| | APPLICATION #07080952 |
| | ELECTRICAL PLAN REVIEW |
| | 310 FLAMINGO DRIVE |
| | 12/10/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | ALTHOUGH THE ELECTRICAL REVIEW WAS PASSED ON 9/12/07, |
| | THESE COMMENTS COME FROM NEW INFORMATION AND DRAWINGS |
| | SUBMITTED ON 11/28/07. |
| | |
| | 1} ELECTRICAL SPECIFICATIONS, SHEET E-0, PART 3 (A), |
| | INDICATES THE COLOR CODING FOR A SINGLE PHASE, 120/240 |
| | VOLT SYSTEM. THE RISER DIAGRAM INDICATES THE SERVICE |
| | BEING 3 PHASE 120/208 SYSTEM, CORRELATE SAME. |
| | |
| | 2} THE PANEL SCHEDULES INDICATE THE PANELS ARE ?FED |
| | FROM UTILITY?, CORRECT TO INDICATE FED FROM MAIN |
| | DISCONNECT.106.1.3 FBC AS AMENDED. |
| | |
| | 3} INDICATE THE BRANCH CIRCUIT CONDUCTOR SIZES ON THE |
| | PANEL SCHEDULE SO THAT COMPLIANCE WITH 310.16 CAN BE |
| | REVIEWED. |
| | |
| | 4} CIRCUIT LPA-5 HAS TWO RECEPTACLES LOCATED ON A |
| | KITCHEN COUNTERTOP AND MUST COMPLY WITH SMALL APPLIANCE |
| | BRANCH CIRCUIT ARTICLES. SEE 210.52(A), 210.52(C), AND |
| | 210.8(A)(6) GFI. |
| | |
| | 5} SEE 210.52(C)(2) FOR ISLAND RECEPTACLE REQUIREMENT, |
| | LOCATE SAME ON PLAN. |
| | |
| | 6} THE MOCP FOR AIR HANDLERS 1,2 AND 4, ON SHEET M.2, |
| | AND THE OCP IN THE PANEL SCHEDULES, SHEET E-0, FOR |
| | THOSE UNITS ARE IN CONFLICT. CORRELATE SAME. |
| | |
| | 7}210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING |
| | AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE |
| | LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT |
| | GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE |
| | GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| | DWELLING. LOCATE SAME ON PLANS. |
| | |
| | 8} CIRCUIT LPA-35 AND LPA-17 MUST BE AFCI PROTECTED PER |
| | 210.12. |
| | |
| | 9} THE ENERGY CERTIFICATIONS SUBMITTED ARE FOR A |
| | WAREHOUSE, SHEET A.1 INDICATES AN R3 BUILDING TYPE. THE |
| | APPLICATION STATES NO CHANGE OF OCCUPANCY. THE GARAGE |
| | IS LABELED ?ACCESSORY TO RESIDENCE?.CORRELATE THESE |
| | DOCUMENTS, DECLARE OCCUPANCY TYPE, IF R3 CHECK THE |
| | CHANGE OF OCCUPANCY BOX ON THE APPLICATION, SUBMIT |
| | ENERGY CALCULATIONS PER 13-600. |
| | |
| | THE ELECTRICAL REVIEW WAS DONE FOR R3 AS INDICATED ON |
| | THE PLAN. PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND |
| | REPLACE WITH CORRECTED ONES WHEN RESUBMITTING. INCLUDE |
| | THEM SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND |
| | TO REVIEW COMMENTS IN WRITING. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |