| Date |
Text |
| 2007-11-02 18:23:39 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. PLANS SHALL BE SUBMITTED IN A MINIMUM OF TWO |
| | COMPLETE SETS. LOOSE SHEETS ARE NOT ACCEPTABLE. SECTION |
| | 106.1. |
| | |
| | 2. DECLARE THE OCCUPANCY. IT APPEARS THAT THESE ARE |
| | WAREHOUSES AND THE RESIDENTIAL AREA DOES NOT MEET THE |
| | DEFINITION OF DWELLING IN AS IT DOES NOT HAVE SLEEPING |
| | PROVISIONS. SECTION 310.2. COMMERCIAL LIVE/WORK DOES |
| | NOT INDICATE THE OCCUPANCY OF THE COMMERCIAL SECTION. |
| | SECTION 106.1.1. |
| | |
| | 3. SHT A-1 THE STORAGE OCCUPANCIES REQUIRES DRINKING |
| | FOUNTAINS AND SERVICES SINKS IF, AS INDICATED ON THE |
| | ENERGY CALCULATIONS, THERE WILL BE FOUR WAREHOUSE BAYS. |
| | PLEASE ALSO INDICATE THE TYPE OF MATERIAL & THE AMOUNT |
| | THAT WILL BE STORED IN THE STORAGE BAYS. MSDS SHEETS |
| | MAY BE REQUIRED AS WELL AS AN EYE WASH/EMERGENCY SHOWER |
| | DEPENDING ON THE RESPONSE OF THIS COMMENT AND THE MSDS |
| | SHEETS. SECTION 106.1.2 & TABLE 403.1. |
| | |
| | 4. SUBMIT AN EXISTING FLOOR PLAN SO THE EXTENT OF THE |
| | WORK CAN BE ESTABLISHED. SECTION 106.1.2, MORE |
| | INFORMATION REQUIRED. |
| | |
| | 5. SHT A.1 THE FUTURE TOILET ROOMS SHALL BE ACCESSIBLE. |
| | SHOW COMPLIANCE WITH SECTIONS 11-4.15, 11-4.16, 11-4.19 |
| | & 11-4.22 WITH ALL SUBSECTIONS AS WELL AS SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING.--SUBMIT DETAILS IN |
| | BOTH A FLOOR PLAN AND ELEVATIONS. |
| | |
| | 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO |
| | THE BUILDING. SECTION 608.13.2. |
| | |
| | 7. SHT P.1 2 WATER CLOSETS ARE NOT INDICATED AS FUTURE |
| | FIXTURES. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 8. SHT P.1 KEY PLAN NOTES #1 IS NOT SHOWN ON THE FLOOR |
| | PLAN. PLEASE INDICATED NOTE #1. SECTION 106.1.2. |
| | |
| | 9. SHT P.1 NO SANITARY OR WATER PIPING ARE SHOWN TO THE |
| | WASH MACHINE. TABLE 403.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |