| 2007-10-22 14:05:07 | 1. BUILDING ADDRESS IS REQUIRED ON THE PROPER BUILDING |
| | ELEVATION. A MINIMUM OF AT LEAST 6" HIGH 1" WIDE |
| | NUMBERS ARE REQUIRED. |
| | |
| | 2. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 3. ELECTRIC POWERED SMOKE DETECTORS ARE REQUIRED WITHIN |
| | THE RESIDENTIAL PORTION OF THE BUILDING. WHEN |
| | ACTIVATED, THE DETECTOR(S) SHALL BE AUDIBLE TO ALERT |
| | PERSONS OF A FIRE EMERGENCY. |
| | |
| | 4. ON M-1 PLANS MAKE REFERENCE TO CARBON DIOXIDE |
| | DETECTORS AND IN OTHER INSTANCES IT CALLS OUT THE |
| | SYMBOL FOR CARBON MONOXIDE DETECTORS. PLEASE CORRECT |
| | PLANS. |
| | |
| | 5. PAGE A-5 DOES NOT MATCH ELECTRICAL DRAWINGS AS THEY |
| | RELATE TO EXIT SIGNS AND EMERGENCY LIGHTING. |
| | |
| | 6. PLANS CALL CLASS C FLAMESPREAD BUT THE PLANS |
| | INDICATE THAT THE BUILDING IS NON FIRE SPRINKLER |
| | PROTECTED. PLEASE CORRECT PLANS AS NECESSARY. |
| | |
| | 7. PLEASE DECLARE MATERIALS PLANNED TO BE STORED IN |
| | STORAGE AREAS. IS ANY FLAMMABLE, COMBUSTIBLE, TOXIC, |
| | POSIONOUS, OR EXPLOSIVE SOLIDS, LIQUIDS, OR GASES |
| | PLANNED TO BE STORED. |
| | |
| | 8. VEHICLES IF PLANNED TO BE STORED IN THESE AREAS, THE |
| | VEHICLES SHALL CONTAIN VERY LITTLE FUEL AND HAVE THE |
| | BATTERY TERMINALS DISCONNECTED. |
| | |
| | 9. PLEASE ILLUSTRATE ANY PORTABLE FIRE EXTINGUISHING |
| | EQUIPMENT PLANNED FOR THE SPACE. |
| | |
| | |