Plan Review Notes
Plan Review Notes For Permit 07080952
Permit Number 07080952
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-22 14:05:071. BUILDING ADDRESS IS REQUIRED ON THE PROPER BUILDING
 ELEVATION. A MINIMUM OF AT LEAST 6" HIGH 1" WIDE
 NUMBERS ARE REQUIRED.
  
 2. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 3. ELECTRIC POWERED SMOKE DETECTORS ARE REQUIRED WITHIN
 THE RESIDENTIAL PORTION OF THE BUILDING. WHEN
 ACTIVATED, THE DETECTOR(S) SHALL BE AUDIBLE TO ALERT
 PERSONS OF A FIRE EMERGENCY.
  
 4. ON M-1 PLANS MAKE REFERENCE TO CARBON DIOXIDE
 DETECTORS AND IN OTHER INSTANCES IT CALLS OUT THE
 SYMBOL FOR CARBON MONOXIDE DETECTORS. PLEASE CORRECT
 PLANS.
  
 5. PAGE A-5 DOES NOT MATCH ELECTRICAL DRAWINGS AS THEY
 RELATE TO EXIT SIGNS AND EMERGENCY LIGHTING.
  
 6. PLANS CALL CLASS C FLAMESPREAD BUT THE PLANS
 INDICATE THAT THE BUILDING IS NON FIRE SPRINKLER
 PROTECTED. PLEASE CORRECT PLANS AS NECESSARY.
  
 7. PLEASE DECLARE MATERIALS PLANNED TO BE STORED IN
 STORAGE AREAS. IS ANY FLAMMABLE, COMBUSTIBLE, TOXIC,
 POSIONOUS, OR EXPLOSIVE SOLIDS, LIQUIDS, OR GASES
 PLANNED TO BE STORED.
  
 8. VEHICLES IF PLANNED TO BE STORED IN THESE AREAS, THE
 VEHICLES SHALL CONTAIN VERY LITTLE FUEL AND HAVE THE
 BATTERY TERMINALS DISCONNECTED.
  
 9. PLEASE ILLUSTRATE ANY PORTABLE FIRE EXTINGUISHING
 EQUIPMENT PLANNED FOR THE SPACE.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX