| 2007-09-26 20:30:19 | BUILDING PLAN REVIEW |
| | PERMIT: 07080952 |
| | ADD: 310 FLAMINGO DRIVE |
| | CONT: ISLAND CONSTRUCTION |
| | TEL: (561)236-9983 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2) PLLEASE SEE NOTES FROM JOHN ROACH IN ZONING THAT A |
| | WORK LIVE LOFT CAN ONLY USE 20% OF THE GROSS FLOOR |
| | AREA, THE PLAN ON SHEET A.1 INDICATES THAT 80 % OF THE |
| | STRUCTURE WOULD BE |
| | STORAGE NOT THE ALLOWABLE 20%. THE OTHER ISSUE FOR A |
| | WORK LIVE LOFT IS THAT IT NEEDS TO MEET THE DEFINITION |
| | OF DWELLING UNIT. DWELLING UNIT . A SINGLE UNIT |
| | PROVIDING COMPLETE, INDEPENDENT LIVING FACILITIES FOR |
| | ONE OR MORE PERSONS, INCLUDING PERMANENT PROVISIONS FOR |
| | LIVING, SLEEPING, EATING, COOKING AND SANITATION. THIS |
| | PLAN LACKS SLEEPING QUARTERS, MAKING IT NOT A DWELLING |
| | UNIT. |
| | PLANS ALSO FAIL TO INDICATE WHICH WINDOWS WILL QUALIFY |
| | AS THE EMERGENCY EGRESS OPENINGS FOR THE SLEEPING |
| | QUARTERS.1025.1/ 1025.2. |
| | |
| | 3) PLEASE CORRECT THE A.0 COVERSHEET WITH REGARDS TO |
| | FLOOD ZONE INFORMATION, THIS IS NOT IN A "AH" FLOOD |
| | ZONE. |
| | |
| | 4) PLEASE PROVIDE TO WHAT LEVEL OF ALTERATION WILL BE |
| | COMPLETED UNDER THIS PERMIT. PROVIDE INFORMATION |
| | ADDITIONAL INFORMATION TO THE APPLICABLE ODES, 2004 FBC |
| | BUILDING W/ 2007 REVISONS |
| | 2004 EXISTING BUILDING CODE W/ 2006 REVISIONS |
| | |
| | 5A) PLANS INDICATE A PROPOSED STORAGE OCCUPANCY, WHAT |
| | TYPE OF MATERIALS WOULD BE STORED THERE?PROVIDE IF |
| | S1, S2 OR HAZARDOUS MATERIALS, AND QUANITIES.SEE TABLE |
| | 302.3.2 FOR HR RATING, NOT A 1 HR WALL IF S1 THEN 3HR |
| | RATED WALL, S2 THEN A 2HR RATED WALL BETWEEN THE |
| | STORAGE OCCUPANCY AND R3 OCCUPANCY. |
| | |
| | 5B) UNDER THE STORAGE OCCUPANCY, IS THIS A SINGLE |
| | TENANT OCCUPANCY OR MULTIPLE TENANT OCCUPANCY? PLANS DO |
| | NOT SHOW EGRESS DOORS IF MULTIPLE STORAGE TENANT. |
| | |
| | 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 6A) ROOFING ASSEMBLIES W/INSULATION |
| | |
| | 7) THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH |
| | THE FOLLOW ITEMS: |
| | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | _X__ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _X__ |
| | CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED. |
| | NO REPORT SUBMITTED. |
| | _X__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| | 2&3___ . |
| | X___ THE SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD |
| | THE FASTENER |
| | RESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISEDFASTENER SPACING, |
| | PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| | ENHANCED FASTENING ALLOWED. |
| | |
| | 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9)THE STORAGE OCCUPANCIES INDICATE A FUTURE TOILET |
| | IN EACH OF THREE BAYS, AT WHAT TIME IS THE FUTURE |
| | TOILET TO BE INSTALLED, IF SHOWN ON THESE PLANS ARE |
| | THEY TO BE PART OF THIS PERMIT. |
| | THEY WILL NEED TO MEET THE REQUIREMENTS FOR |
| | ACCESSIBILITY FOR HANDICAPPED RESTROOMS IF SEPERATE |
| | TENANTS. 11-4.22 AND OR 11-4.16. |
| | |
| | 10) DISCREPANCIES, A-1 VS E -1 SHEET E-1 IS MISSING THE |
| | REQUIRED EGRESS DOORS FORT HE STORAGE OCCUPANCIESTHAT |
| | ARE SHOWN ON A-1. SHEET A-2 ALSO DOESN'T INDICATE THE |
| | EGRESS DOORS. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 11)A.1 TOLIET ROOMS DO NOT INDICATE ANY WINDOWS NOR |
| | DO THEY SHOW ON E2 ANY LIGHT FIXTURES WITHIN THE |
| | RESTROOM FACILITIES1205.3 ARTIFICIAL LIGHT. |
| | |
| | 12)THE ENERGY CALCS INPUT DATA REPORT SHEET 3 |
| | &INDICATES THERE TO BE LIGHTS WITHIN THEWAREHOUSE |
| | RESTROOM A 50 WATT FIXTURE WHERE AS THE E2 SHEET |
| | DOESN'T INDICATE ANY 50 WATT FIXTURES NOR DOES THE |
| | LIGHTING PLAN CORRELATE WITH THE LIGHTING LEGEND. |
| | 13-415.2 |
| | |
| | 13) WHEN REVIEWING THE ENERGY CALCS FOR THE LIGHTING |
| | SHEETS 2& 3 OF THE INPUT DATA REPORT NONE OF THE |
| | FIXTURES MATCH THE FIXTURE LEGEND FOUND ON SHEET E-2 |
| | SEE 13-415.2. |
| | |
| | 14) SHEET E-2 IS MISSING THE EGRESS DOORSSHOEN ON A-2 |
| | AND EXIT LIGHTING FOR THE (3) STORAGE BAYS. 2004 FBC |
| | SECTION 1006. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |