| 2007-10-16 11:56:10 | **** PROVISO/REVISION NEEDED**** |
| | |
| | |
| | 1) NOTE:PLANS MISSING LIGHTING POWER DENSITIES FOR |
| | NEW OFFICES PER 13-415.2 |
| | |
| | 2) NOTE: PLANS MISSING MAXIMUM TIMES FOR OS DEVICES PER |
| | 13-415.1.ABC.1.1(MAX 30MINS) |
| | |
| | 3) NOTE: PLANS STILL INDICATE THE TELCO ROOM AS |
| | EXISTING ALONG WITH AN IT PANEL IN WHICH THIS OFFICE |
| | HAS NO RECORD OF THIS WORK BEING PERMITTED IN OUR |
| | CURRENT SYSTEM GOING BACK ALMOST 10YEARS. |
| | THE CONTRACTOR HAS NOW VOIDED PREVIOUS APPLIED FOR |
| | PERMIT FOR IT ROOM EXPANSION. (# 06101010) |
| | THE ENGINEER OF RECORD KNOWS OF PREVIOUS WORK APPLIED |
| | FOR UNDER #06101010. |
| | THE SERVICE AND WORK SHOWN AS *EXISTING* SHALL BE |
| | VERIFIED IN FIELD BY INSPECTION SERVICES STAFF. ALL |
| | INFORMATION WAS FORWARDED TO BOTH ASSISTANT BUILDING |
| | OFFICIALS TO BE ADDRESSED. |
| | |
| | 4) NOTE: PLEASE REVISE PLANS AS NEEDED FOR NOTES #1 AND |
| | 2 BEFORE ROUGH ELECTRICAL INSPECTION UNDER THE |
| | PERMITTED SCOPE OF WORK. |
| | ANY CORRECTION NOTICES ISSUED IN FIELD FOR OTHER SCOPE |
| | OF WORK WILL BE ADDRESSED AT THAT TIME. |
| | ** IF PLANS COME BACK FOR CORRECTIONS FROM ANY OTHER |
| | TRADES, PLEASE ADDRESS AT THAT TIME, THIS WILL |
| | ALLEVIATE THE NEED FOR A REVISION AT A LATER DATE |
| | BEFORE ROUGH. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |