Plan Review Notes
Plan Review Notes For Permit 07080911
Permit Number 07080911
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-01 16:34:06****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.CONTRACTOR
 STATES THAT HE WILL INSTALL 12 ROWS AT 4" OC.THE
 SHEET IS 39" WIDE; HAVING 12 ROWS CREATES ROWS WHICH
 ARE LESS THAN 4" APART.THIS IS NOT ALLOWED AS PER
 RAS117 (FASTENER SPACING TO BE A MINIMUM OF 4").
 PLEASE SELECT AN APPROVED ASSEMBLY AND SPECIFY ENHANCED
 FASTENING IN ACCORDANCE WITH RAS117.CALCULATIONS MAY
 BE REQUIRED.
  
 NEW COMMENT:
  
 ALL INFORMATION REQUIRED ON THE RESUB SHEET.YOU DID
 NOT INCLUDE THE PERMIT NUMBER, BUT THIS IS HOW WE TRACK
 THE APPLICATIONS AND SUBMITTALS.PLEASE ALWAYS INCLUDE
 ALL REQUIRED INFORMATION.
  
  