| 2007-10-01 16:34:06 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| | LIMITATIONS. |
| | |
| | _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES.CONTRACTOR |
| | STATES THAT HE WILL INSTALL 12 ROWS AT 4" OC.THE |
| | SHEET IS 39" WIDE; HAVING 12 ROWS CREATES ROWS WHICH |
| | ARE LESS THAN 4" APART.THIS IS NOT ALLOWED AS PER |
| | RAS117 (FASTENER SPACING TO BE A MINIMUM OF 4"). |
| | PLEASE SELECT AN APPROVED ASSEMBLY AND SPECIFY ENHANCED |
| | FASTENING IN ACCORDANCE WITH RAS117.CALCULATIONS MAY |
| | BE REQUIRED. |
| | |
| | NEW COMMENT: |
| | |
| | ALL INFORMATION REQUIRED ON THE RESUB SHEET.YOU DID |
| | NOT INCLUDE THE PERMIT NUMBER, BUT THIS IS HOW WE TRACK |
| | THE APPLICATIONS AND SUBMITTALS.PLEASE ALWAYS INCLUDE |
| | ALL REQUIRED INFORMATION. |
| | |
| | |