| Plan Review Notes For Permit 07080904 |
| Permit Number |
07080904 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-06 09:00:04 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. | | | | | | 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 | | | RESIDENTIAL FLORIDA BUILDING CODE. PLEASE NOTE THIS | | | REQUIREMENT ON THE PLANS. | | | | | | 4}REGARDING THE ELECTRICAL PANEL IN THE CLOSET, OR | | | BATHROOM, REFER TO NEC 2005, ARTICLE 240.24 (D) NOT IN | | | VICINITY OF EASILY IGNITIBLE MATERIAL OVERCURRENT | | | DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY | | | IGNITIBLE MATERIAL, SUCH AS IN CLOTHES CLOSETS. | | | EXAMPLES OF LOCATIONS WHERE COMBUSTIBLE MATERIALS MAY | | | BE STORED ARE LINEN CLOSETS, PAPER STORAGE CLOSETS, AND | | | CLOTHES CLOSETS. | | | (E) NOT LOCATED IN BATHROOMS IN DWELLING UNITS AND | | | GUEST ROOMS OR GUEST SUITES OF HOTELS AND MOTELS, | | | OVERCURRENT DEVICES, OTHER THAN SUPPLEMENTARY | | | OVERCURRENT PROTECTION, SHALL NOT BE LOCATED IN | | | BATHROOMS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|