 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. PLEASE NOTE THIS
 REQUIREMENT ON THE PLANS.
  
 4}REGARDING THE ELECTRICAL PANEL IN THE CLOSET, OR
 BATHROOM, REFER TO NEC 2005, ARTICLE 240.24 (D) NOT IN
 VICINITY OF EASILY IGNITIBLE MATERIAL OVERCURRENT
 DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY
 IGNITIBLE MATERIAL, SUCH AS IN CLOTHES CLOSETS.
 EXAMPLES OF LOCATIONS WHERE COMBUSTIBLE MATERIALS MAY
 BE STORED ARE LINEN CLOSETS, PAPER STORAGE CLOSETS, AND
 CLOTHES CLOSETS.
 (E) NOT LOCATED IN BATHROOMS IN DWELLING UNITS AND
 GUEST ROOMS OR GUEST SUITES OF HOTELS AND MOTELS,
 OVERCURRENT DEVICES, OTHER THAN SUPPLEMENTARY
 OVERCURRENT PROTECTION, SHALL NOT BE LOCATED IN
 BATHROOMS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  