| Plan Review Notes For Permit 07080894 |
| Permit Number |
07080894 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-15 10:57:34 | DENIED; | | | 1.AUTOMATIC CLOTHES WASHER NOT SHOWN ON FLOOR PLAN PAGE | | | A-2. | | | 2. TWO P-1'S SUBMITED, REMOVE THE SHEET DRAWN BY GLACE | | | AND COMPANY. | | | 3. REVIEW OF RISER DIAGRAM BY BRUCE MILLER; | | | A. AUTOMATIC CLOTHES WASHER NOT VENTED, ALSO | | | CLEANOUT IS REQUIRED AT 48" OFF FINISH FLOOR. | | | B. DISHWASHER TO DISCHARGE INDIRECTLY INTO THE | | | TAIL PIECE OF THE KITCHEN SINK. | | | C. BATHROOM # 1 CAN NOT BE INSTALLED AS DRAWN. | | | A BATHROOM GROUP CAN NOT BE PART OF THE BUILDING DRAIN. | | | SEE FBC-2004 PLUMBING SECTION 909.1 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|