| 2007-09-07 11:49:38 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE SERVICE LOCATION DOES NOT MEET THE CLEARANCE |
| | REQUIREMENTS OF 110.26. THE CLEAR SPACE (3?) BECAUSE OF |
| | THE STEPS, AND THE 30? WIDTH REQUIREMENT WITH REGARD TO |
| | THE CONDENSING UNIT, THE DISCONNECT AND THE METER. |
| | |
| | 2} PROVIDE THE CONDUIT SIZE, CONDUCTOR NUMBER AND SIZE |
| | FROM THE METER TO THE DISCONNECT ON THE RISER. THIS |
| | COMMENT IS MADE TO INSURE THAT NO GROUNDING CONDUCTOR |
| | PARALLELS THE NEUTRAL PRIOR TO THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 3} THE GROUNDING ELECTRODE SYSTEM MUST COMPLY WITH |
| | 250.50. SEE 250.52(A)(3) FOR FOOTER STEEL. |
| | |
| | 4}PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. COMPLIANCE WITH THIS ARTICLE MUST |
| | BE CLEAR IN THE DESIGN STAGE AND THAT RATING INDICATED |
| | ON THE PLAN. |
| | |
| | 5} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED |
| | UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY |
| | IN THE FIELD AND RECORD RETENTION PER 106.1.3 FBC AS |
| | AMENDED. |
| | |
| | 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A),210.52(C) AND 210.8(A)(6) GFI. THIS APPLIES |
| | TO ALL COUNTERTOPS AND THE ISLAND. |
| | |
| | 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| | 210.52(A)(2). SEE BEDROOM #2 WALL AREA BETWEEN THE DOOR |
| | AND CLOSET. |
| | |
| | 8} THE ENGINEER OF RECORD MUST PROVIDE A TITLE BLOCK |
| | WITH INFORMATION PER 61G15-23.002(2) FAC |
| | |
| | NOTE: REGARDING THE DISCONNECTING MEANS FOR THE WATER |
| | HEATER. SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, |
| | AND 422.31(B) FOR HARDWIRE REQUIREMENTS AND 422.17 FOR |
| | COMBUSTIBLE MATERIALS AND APPLIANCES. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | WILLIAM R. TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |