Plan Review Notes
Plan Review Notes For Permit 07080894
Permit Number 07080894
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-07 11:49:38 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE SERVICE LOCATION DOES NOT MEET THE CLEARANCE
 REQUIREMENTS OF 110.26. THE CLEAR SPACE (3?) BECAUSE OF
 THE STEPS, AND THE 30? WIDTH REQUIREMENT WITH REGARD TO
 THE CONDENSING UNIT, THE DISCONNECT AND THE METER.
  
 2} PROVIDE THE CONDUIT SIZE, CONDUCTOR NUMBER AND SIZE
 FROM THE METER TO THE DISCONNECT ON THE RISER. THIS
 COMMENT IS MADE TO INSURE THAT NO GROUNDING CONDUCTOR
 PARALLELS THE NEUTRAL PRIOR TO THE FIRST MEANS OF
 DISCONNECT.
  
 3} THE GROUNDING ELECTRODE SYSTEM MUST COMPLY WITH
 250.50. SEE 250.52(A)(3) FOR FOOTER STEEL.
  
 4}PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. COMPLIANCE WITH THIS ARTICLE MUST
 BE CLEAR IN THE DESIGN STAGE AND THAT RATING INDICATED
 ON THE PLAN.
  
 5} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED
 UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY
 IN THE FIELD AND RECORD RETENTION PER 106.1.3 FBC AS
 AMENDED.
  
 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A),210.52(C) AND 210.8(A)(6) GFI. THIS APPLIES
 TO ALL COUNTERTOPS AND THE ISLAND.
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). SEE BEDROOM #2 WALL AREA BETWEEN THE DOOR
 AND CLOSET.
  
 8} THE ENGINEER OF RECORD MUST PROVIDE A TITLE BLOCK
 WITH INFORMATION PER 61G15-23.002(2) FAC
  
  NOTE: REGARDING THE DISCONNECTING MEANS FOR THE WATER
 HEATER. SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS,
 AND 422.31(B) FOR HARDWIRE REQUIREMENTS AND 422.17 FOR
 COMBUSTIBLE MATERIALS AND APPLIANCES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718