Plan Review Notes
Plan Review Notes For Permit 07080894
Permit Number 07080894
Review Stop B
Sequence Number 1
Notes
Date Text
2007-09-29 14:08:49 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAYBE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPTATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $773.37FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 4)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 5)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 7)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER
 R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES
  
 8)PROVIDE SCHEDULE FOR PRECAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC &
 703.7.3 FBC RES. FOR MIN BEARING
  
 9)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
  
 10)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH
 R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE
 INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD
  
 11)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 12)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 13)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 NOTE: PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENT
 AND CLADDING PRODUCTS (FRENCH DOORS, WINDOWS, WINDOW
 MULLIONS, ROOFING (MODIFIED & SHINGLE), VINYL SOFFIT &
 SIDING, CONCRETE LINTELS, ROOF HATCH, ETC.
  
 14)PROVIDE SIMPSON TIE CONNECTOR SCHEDULE FOR ALL
 FRAMING CONNECTIONS THAT INCLUDES FLORIDA STATEWIDE
 PRODUCT APPROVAL #'S OR SUBMIT THE PRODUCT APPROVALS
 FOR THE REQUIRED CONNECTORS
  
 15)SUBMIT SHOP DRAWINGS FOR THE SPIRAL STAIRS THAT
 SHOW COMPLIANCE WITH R311.5.8.1 FBC RES.
  
 16)PROVIDE CORRECT SIZES FOR WINDOWS IN THE WINDOW
 SCHEDULE AS THEY DO NOT MATCH BUILDING ELEVATIONS, BE
 SURE TO NOTE OPENINGS THAT REQUIRE (2) UNITS TO BE
 MULLED TOGETHER. ALSO VERIFY WINDOW TYPES ELEVATION HAS
 SINGLE HUNG AND SCHEDULE HAS CASEMENT.
  
 17)PROVIDE ALL DOOR AND WINDOW DESIGN PRESSURES
  
 18)PROVIDE WOOD FRAME OPENING DETAIL C/W FRAMING
 CONNECTOR THAT WILL BE USED AT WINDOW OPENINGS.
  
 19)PROVIDE DETAIL FOR POST ATTACHMENT AT MASTER
 BEDROOM BALCONY, GUARDRAIL TO MEET CONCENTRATED LOAD
 REQUIREMENTS OF 200 POUNDS PER SQUARE FOOT APPLIED IN
 ANY DIRECTION PER R303.5 FBC RES.
  
 20)CLARIFY BB-1 ON FOUNDATION PLAN SHEET A-3, SECTION
 3/A-11 STATES THAT STEM WALL IS SOLID GROUT BELOW GRADE
 IS TOP OF STEM WALL A BOND BEAM AS IT IS NOT IN THE
 BEAM SCHEDULE. ALSO 3/A11 AND WALL SECTION C/A-5 SHOW
 DIFFERENT FLOOR JOIST CONNECTIONS
  
 21)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  