2007-10-10 16:07:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)PLEASE READ FBC EB 505.1 AND FBC R310.WHAT TYPE
 OF WINDOWS ARE EXISTING?IT IS NOT CLEAR IF THE NEW
 37X50 HORIZONTAL ROLLER WINDOWS ARE COMPILANT WITH THE
 REQUIREMENTS/EXCEPTION OF FBC EB505.1.IF THERE ARE
 CURRENTLY SINGLE HUNG WINDOWS INSTALLED, YOU ARE
 REDUCING THE WIDTH BY MORE THAN 5%.PLANS ARE TO SHOW
 CODE COMPLIANCE.CODE COMPLIANCE CANNOT BE DETERMINED
 BASED ON THE INFORMATION PROVIDED.
  
 3RD REVIEW - PROVIDE WINDOW CLEAR OPENING DIMENSIONS TO
 SHOW COMPLIANCE WITH EMERGENCY EGRESS REQUIREMENTS FBC
 EB 505.1.
  
 A SET HAS BEEN RETAINED.
  