2007-09-21 16:12:08DENIED
 REFERENCE:
 ** FBC-2004 W/2006 REVISIONS SECTIONS 424.2 AND R4101
 SWIMMING POOLS.
 ** FBC-2004 PLUMBING WITH 2006 REVISIONS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 1: SALT GENERATOR IS MISSING FROM THE
 EQUIPMENT LAYOUT AND LEGEND. PER FBC-2004 WITH 2006
 REV. SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. SHEET 1: PLEASE CORRELATE AND CORRECT THE SPA LEGEND
 WITH THE MAIN DRAIN DETAIL. THE SPA LEGEND INDICATES
 (2) 8" MAIN DRAINS BUT THE MAIN DRAIN DETAIL IS
 INDICATING 9" MAIN DRAINS. CODE REFERENCE, FBC-2004
 WITH 2006 REVISIONS SECTION 106.1.1.
  
 3. SHEET 1: PLEASE CORRELATE AND CORRECT THE SPA LEGEND
 THERAPY JETS AMOUNT WITH THE POOL SPECIFICATIONS AND
 PLANS. POOL SPECIFICATIONS AND PLANS ARE INDICATING
 (10) THERAPY JETS. THE SPA LEGEND IS INDICATING (6)
 THERAPY JETS. CODE REFERENCE, FBC-2004 WITH 2006
 REVISIONS SECTION 106.1.1.
  
 4. SHEET 1: PLEASE CLARIFY THE AUTO-FILL LINE SIZE. THE
 11/2" IS CONFUSING, IS IT AN 1-1/2" AUTO-FILL LINE OR
 (1) 1/2" AUTO-FILL LINE. CODE REFERENCE FBC-2004 WITH
 2006 REVISONS SECTION 106.1.1.
  
 5. SHEET 1: PLEASE ADD TO NOTES THE FOLLOWING
 "AUTO-FILL LINE TIE IN TO POTABLE WATER TO BE BY A
 LICENSED PLUMBING CONTRACTOR AND BE PROTECTED FROM
 CROSS CONNECTION BY FBC-2004 W/2006 REV. SECTION 608."
  
 6. HEAT PUMP MANUFACTURE SHEETS:
 FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 NOTE: THE SUBMITTED HEAT PUMP MANUFACTURE SHEETS DO NOT
 INDICATE A LISTING. PLEASE DO THIS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEET BY THIS PLAN EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  