| 2007-09-21 16:12:08 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 W/2006 REVISIONS SECTIONS 424.2 AND R4101 |
| | SWIMMING POOLS. |
| | ** FBC-2004 PLUMBING WITH 2006 REVISIONS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET 1: SALT GENERATOR IS MISSING FROM THE |
| | EQUIPMENT LAYOUT AND LEGEND. PER FBC-2004 WITH 2006 |
| | REV. SECTION 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2. SHEET 1: PLEASE CORRELATE AND CORRECT THE SPA LEGEND |
| | WITH THE MAIN DRAIN DETAIL. THE SPA LEGEND INDICATES |
| | (2) 8" MAIN DRAINS BUT THE MAIN DRAIN DETAIL IS |
| | INDICATING 9" MAIN DRAINS. CODE REFERENCE, FBC-2004 |
| | WITH 2006 REVISIONS SECTION 106.1.1. |
| | |
| | 3. SHEET 1: PLEASE CORRELATE AND CORRECT THE SPA LEGEND |
| | THERAPY JETS AMOUNT WITH THE POOL SPECIFICATIONS AND |
| | PLANS. POOL SPECIFICATIONS AND PLANS ARE INDICATING |
| | (10) THERAPY JETS. THE SPA LEGEND IS INDICATING (6) |
| | THERAPY JETS. CODE REFERENCE, FBC-2004 WITH 2006 |
| | REVISIONS SECTION 106.1.1. |
| | |
| | 4. SHEET 1: PLEASE CLARIFY THE AUTO-FILL LINE SIZE. THE |
| | 11/2" IS CONFUSING, IS IT AN 1-1/2" AUTO-FILL LINE OR |
| | (1) 1/2" AUTO-FILL LINE. CODE REFERENCE FBC-2004 WITH |
| | 2006 REVISONS SECTION 106.1.1. |
| | |
| | 5. SHEET 1: PLEASE ADD TO NOTES THE FOLLOWING |
| | "AUTO-FILL LINE TIE IN TO POTABLE WATER TO BE BY A |
| | LICENSED PLUMBING CONTRACTOR AND BE PROTECTED FROM |
| | CROSS CONNECTION BY FBC-2004 W/2006 REV. SECTION 608." |
| | |
| | 6. HEAT PUMP MANUFACTURE SHEETS: |
| | FBC-2004 SEC. 424.2.14.1, OR |
| | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | SHEETS REQUIRED, PLEASE SUBMIT) |
| | NOTE: THE SUBMITTED HEAT PUMP MANUFACTURE SHEETS DO NOT |
| | INDICATE A LISTING. PLEASE DO THIS ON THE RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK |
| | ON THE INDICATED PLAN SHEET BY THIS PLAN EXAMINER FOR |
| | REFERENCE FOR THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |