| Plan Review Notes For Permit 07080846 |
| Permit Number |
07080846 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-28 16:54:35 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)THE ENGINEER'S LETTER STATES THAT THE SYSTEM HAS A | | | DESIGN PRESSURE OF -45, CONTRACTOR HIGHLIGHTED A SYSTEM | | | FOR -52.5.CONFIRM WHICH ASSEMBLY YOU'RE USING. | | | | | | 2.)ENGINEER'S LETTER STATES THAT 9"/9" IS TO BE USED | | | IN THE BALANCE OF THE ROOF (OTHER THAN CORNERS), BUT | | | THE PERIMETER REQUIREMENT IS -59.2, ENHANCED FASTENING | | | FOR ZONE 2 REQUIRED. |
|