Plan Review Notes
Plan Review Notes For Permit 07080840
Permit Number 07080840
Review Stop E
Sequence Number 2
Notes
Date Text
2008-09-16 16:07:05** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS DO NOT
 COORDINATE WITH THE ELECTRICAL SHEETS SUBMITTED BY THE
 ELECTRICAL CONTRACTOR.
 FOR EXAMPLE: NOT ALL FIXTURES NOTED BY ELECTRICIAN IS
 ON PLANS. MISSING FIXTURE AND CONTROL OF 175W FIXTURE.
 FOR EXAMPLE: PLEASE SEE ARCHITECTURAL PLANS CALL FOR
 LIGHTING TO BE ON TIMERS. IF THIS IS THE CASE THEY ARE
 REQUIRED TO MEET FBC 13-415.1.ABC.1.4. THE ELECTRICAL
 CONTRACTOR HAS NOTES WHICH STATE PHOTO-CELL CONTROLLED.
  
 THE PLANS NEED TO COORDINATE. THE ARCHITECTURAL PLANS
 NEEDS TO SHOW THE COMPLIANCE AND INFORMATION SET FORTH
 BY THE ELECTRICAL CONTRACTOR AND COORDINATION NEEDS TO
 BE COMPLETED. ONCE THIS IS DONE PLEASE BE SURE TO
 COMPLETE CIRCUITING, FIXTURE TYPES ON A LEGEND ETC.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  