| 2008-09-16 16:07:05 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS DO NOT |
| | COORDINATE WITH THE ELECTRICAL SHEETS SUBMITTED BY THE |
| | ELECTRICAL CONTRACTOR. |
| | FOR EXAMPLE: NOT ALL FIXTURES NOTED BY ELECTRICIAN IS |
| | ON PLANS. MISSING FIXTURE AND CONTROL OF 175W FIXTURE. |
| | FOR EXAMPLE: PLEASE SEE ARCHITECTURAL PLANS CALL FOR |
| | LIGHTING TO BE ON TIMERS. IF THIS IS THE CASE THEY ARE |
| | REQUIRED TO MEET FBC 13-415.1.ABC.1.4. THE ELECTRICAL |
| | CONTRACTOR HAS NOTES WHICH STATE PHOTO-CELL CONTROLLED. |
| | |
| | THE PLANS NEED TO COORDINATE. THE ARCHITECTURAL PLANS |
| | NEEDS TO SHOW THE COMPLIANCE AND INFORMATION SET FORTH |
| | BY THE ELECTRICAL CONTRACTOR AND COORDINATION NEEDS TO |
| | BE COMPLETED. ONCE THIS IS DONE PLEASE BE SURE TO |
| | COMPLETE CIRCUITING, FIXTURE TYPES ON A LEGEND ETC. |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |