| 2007-09-11 16:56:13 | COMMERCIAL AWNINGS BUILDING REVIEW FIRST CHECKLIST. | | | REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- INSTALLATION OF AWNINGS IS OUT OF THE SCOPE OF WORK | | | CONTRACTOR'S LICENSE ES12000166. THIS LICENSE IS TO | | | INSTALL SIGNS, NOT AWNINGS.CONTRACTOR WHO CAN | | | INSTALLAWNINGS NEEDSTO APPLY FOR THE PERMIT. | | | | | | 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. | | | IN ADDITION, ENGINEERING FEES SHALL BE INCLUDED. | | | UPDATE VALUE OR IT WILL BE ESTIMATED AS REQUIRED BY | | | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 3- FABRIC USED SHALL BE FLAME RESISTANT AS REQUIRED BY | | | SEC. 3105.3.1FBC 2004. PROVIDE COMPLETE | | | SPECIFICATIONS TO SHOW COMPLIANCE WITH THIS SECTION. | | | | | | 4- ENGINEER TO CLEARLY INDICATE WHICH DESIGN CRITERIA | | | WAS USED FOR THE FRAMING AND FABRIC AS REQUIRED BY SEC. | | | 3105.4.2 FBC 2004.IF DESIGNING WITH FABRIC TO BE | | | REMOVED WITH A QUICK REMOVAL OR BREAKAWAYMEMBRANE, | | | THEN COMPLETE SERIES OF PICTURES IS REQUIRED TO BE | | | SUBMITTED FOR BUILDING OFFICIAL APPROVAL. | | | | | | 5- PROVIDE COMPLETE DIMENSIONS FOR INTERIOR TRUSSES. | | | AWNING FRAME SECTION DETAIL SHOWN CALLS FOR "TO BE | | | DET".NEED TO PROVIDE COMPLETE DIMENSIONS. THIS IS | | | PART OF THE ENGINEERING DESIGN. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|