Plan Review Notes
Plan Review Notes For Permit 07080806
Permit Number 07080806
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-16 14:41:14RESIDENTIAL SHUTTERS BUILDING REVIEW SECOND CHECKLIST.
  
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND BC
 2004 WITH 2007 REVISIONS.
  
 1- STORM SHUTTERS INSTALLATION SCHEDULE SUBMITTED:
 A) PROVIDE 2 COPIES.ONLY ONE WAS SUBMITTED.SEC.
 106.1 CITY AMENDMENTS TO FBC 2004.
  
 B) THERE ARE 2 DIFFERENT PRODUCT APPROVALS
 SUBMITTED.FL 722-R1 AND NOA 06-0110.04ARE 2
 DIFFERENT PRODUCT APPROVALS.SUBMIT ONLY ONE COMPLETE
 PACKAGE. EG: IF SUBMITTING THE FL722-R1, THEN PROVIDE
 DRAWINGS THAT WERE SUBMITTED TO GET THE FLORIDA PRODUCT
 APPROVAL.OTHERWISE, PROVIDE THE NOA ALONE.
  
 C) BUILDING HEIGHT CAN'TBE 8'-1".SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.REVISE AS REQUIRED. SEE
 PLANS.
  
 D) REVISE OPENING SIZE FOR OPENING #1. SEE KEY
 PLAN.
  
 E) INFORMATION SHOWN ON INSTALLATION SCHEDULE
 DOESN'T MATCH INFORMATION HIGHLIGHTED ON THE STORM
 SHUTTERS DRAWINGS. COORDINATE INFORMATIONAS REQUIRED
 TO MATCH. EG: CHECK ANCHOR TYPE AND SPACING, MOUNTING
 CONDITIONS (WALL MOUNTED, BUILD OUT, ETC.),SUBSTRATE
 (CONCRETE BLOCK OR CONCRETE), ETC.
  
 F) CLARIFY INFORMATION ON COLUMN 4. WHAT'S WALL
 B?.THIS COLUMN IS DESIGNED TO SPECIFY SHUTTER
 MOUNTING CONDITIONS. EG: WALL MOUNT, BUILD OUT, ETC.
 SEE SHUTTERS DRAWINGS FOR SPECIFICMOUNTING CONDITIONS
 TO BE USED.THIS HELPS TO IDENTIFY WHICH ANCHOR
 CONNECTION TYPE NEEDS TO BE USED IN THE ANCHOR SCHEDULE
 SHOWN ON PAGE 5 OF 7.
  
 G) SPECIFYBOTH DESIGN PRESSURES. POSITIVE AND
 NEGATIVE.SCHEDULE SUBMITTED ONLY IDENTIFIES THE
 POSITIVE DESIGN PRESSURES. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 H) SPECIFY SHUTTER GLASS SEPARATION. SEE PAGE 4 OF
 DRAWINGS SUBMITTED.
  
 I) SPECIFY ANCHOR SPACING AT BOTTOM OF SHUTTER. ONLY
 TOP ONE WAS SPECIFIED.
  
 J) PROVIDE COMPLETE INFORMATION REGARDING CENTER
 BOLTS.SHUTTER DRAWINGS SUBMITTED DON'T SPECIFY ANY
 CENTER BOLTS. WHERE IS THIS INFORMATION TAKEN FROM?.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 K) INSTALLATION SCHEDULESUBMITTED CALLS FOR
 CONCRETE BLOCK AS THE SUBSTRATE TO RECEIVE THE STORM
 PANELS, WHILEANCHOR SCHEDULE ON PAGE 5 OF 7 THE
 CONCRETE COLUMN WAS HIGHLIGHTED.REVISE INFORMATION AS
 REQUIRED TO MATCH.ANCHORSPACING IS DIFFERENT FOR
 CONCRETE AND FOR CONCRETE BLOCK.
  
 L) REVISE ANCHOR SPACING FOR OPENING #7 AND #12. SEE
 ANCHOR SCHEDULE ON SHEET 5 OF 7.
  
 2- THERE IS A REVIEW AND APPROVED STAMP ON FLORIDA
 PRODUCT APPROVAL FL722-R1.DESIGNER OF RECORD WHO
 REVIEWED AND APPROVED THIS PRODUCT APPROVAL NEEDS TO
 PROVIDE HIS NAME. OTHERWISE, THERE IS NO WAY OF KNOWING
 WHO REVIEW AND APPROVED THE PRODUCT APPROVAL. AND ,
 THIS DECEIVES THE PURPOSE OF HAVING THE DESIGNER OF
 RECORD APPROVING THE PRODUCT APPROVALS.
 ***NOTE:MAKE SURE SELECTED PRODUCT APPROVAL(SEE
 ITEM 1(B)ABOVEGETS REVIEWED AND APPROVED IN WRITING
 (NOT SIGNING AND SEALING)BY THE DESIGNER OF RECORD AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 UPDATE VALUE AS REQUIRED. SEC. 108.3 CITY AMENDMENTS TO
 FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712