| 2007-09-07 16:14:41 | RESIDENTIAL SHUTTERS BUILDING REVIEW FIRST CHECKLIST. | | | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 1- PROVIDE A COMPLETE INSTALLATIONSCHEDULE. SEE | | | ATTACHED CITY SAMPLE.COMPLETELYFILL OUT ALL THE | | | INFORMATION INTHEINSTALLATION SCHEDULETO PROPERLY | | | VERIFY COMPLIANCE WITH PRODUCT APPROVAL PROPOSED | | | INSTALLATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | 2- CLEARLY MARK ON SHUTTERSDRAWINGS SPECIFIC MOUNTING | | | CONDITIONS (EG: WALL MOUNT, ETC.)ALSO, CLEARLY MARK | | | SPECIFIC ANCHOR TYPE AND SPACING TO BE USED ACCORDING | | | TO THE DESIGN PRESSURES, EDGE DISTANCE, CONNECTION | | | TYPE, PANEL SPAN AND STRUCTURE TO BE ATTACHED TO | | | (CONCRETE OR CONCRETE BLOCK).SEE ANCHOR SCHEDULE ON | | | SHEET 5 OF 7 OFNOA NO 06-0110.04 SUBMITTED. SEC. | | | 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. | | | UPDATE VALUE OR IT WILL BE UPDATEDAS REQUIRED BY SEC. | | | 108.3 OF CITY AMENDMENTS TO FBC 2004. | | | | | | 4- CORRECT VALUE WILL BE MORE THAN $2500.RECORDED | | | NOTICE OF COMMENCEMENT WILL BE REQUIRED BY SEC. 713.13 | | | FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|