| Plan Review Notes For Permit 07080804 |
| Permit Number |
07080804 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2008-04-30 16:40:50 | | | | | | | DENIED | | | | | | 1)PROVIDE A KEY PLAN WITH THE OPENINGS NUMBERED TO | | | COINCIDE WITH THE SHUTTER SCHEDULE OPENING NUMBERS, | | | THIS IS REQUIRED FOR INSPECTIONS. PLEASE NOTE THAT THE | | | OPENINGS ON THE SHUTTER SCHEDULE SEEM TO HAVE NO ORDER | | | IN RELATION TO DRAWINGS | | | | | | 2)PRESSURES FOR OPENINGS SHOULD MATCH THOSE ON SHEET | | | 1.3 OF DRAWINGS, IF LEFT AS IS, OPENING # 8 WILL NOT | | | WORK AS MAX DESIGN PRESSURE ALLOWED FOR THIS SHUTTER | | | SPAN IS -42 PSF PER SHEET # 2 OF PRODUCT APPROVAL | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|