Plan Review Notes
Plan Review Notes For Permit 07080804
Permit Number 07080804
Review Stop E
Sequence Number 3
Notes
Date Text
2008-03-12 15:55:53 
  
  
  
 PROVISO
  
 THESE ISSUES MUST BE CORRECTED AND PLANS RESUBMITTED
 FOR REVIEW PRIOR TO CALLING A ROUGH ELECTRICAL
 INSPECTION.
  
 1} BATH CIRCUITS ARE REQUIRED TO HAVE A 20 AMP
 RECEPTACLE PER 210.11(C) (3), LOCATED PER 210.52(D),
 AND BE GFI PROTECTED PER 210.8(A) (1). CIRCUIT #17 IN
 THE MASTER BATH IS NOT RATED ON THE PANEL SCHEDULE,
 THEY COULD BE ON 23 AS THAT CIRCUIT MEETS THE INTENT OF
 THE EXCEPTION 210.11(C) (3).
  
 2} THE "EXISTING BATH", SAME COMMENT AS ABOVE WITH
 CIRCUITS19 AND 25.
  
 3} PER 210.52(B) (1) & (2), THE CIRCUITS IN THE DINING
 ROOM (# 27)MUST BE 20 AMP AS IT IS, BUT MUST BE
 LABLED "DINING ROOM", NOT "GENERAL LIGHTING. ALSO
 "SHALL HAVE NO OTHER OUTLETS" MEANS THE LIVING ROOM IS
 IN VIOLATION BEING ON THE SAME CIRCUIT.
  
 4}THE LIGHTING IN THE KITCHEN SHALL NOT BE ON A SMALL
 APPLIANCE CIRCUIT, 210.52(B) (2).
  
 5} CIRCUIT #6 IS LABLED "COOK TOP" ON THE SCHEDULE AND
 "DOUBLE OVEN" ON THE PLAN, CORRELATE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718