| Notes |
| Date |
Text |
| 2008-03-12 15:55:53 | | | | | | | | | | | | | PROVISO | | | | | | THESE ISSUES MUST BE CORRECTED AND PLANS RESUBMITTED | | | FOR REVIEW PRIOR TO CALLING A ROUGH ELECTRICAL | | | INSPECTION. | | | | | | 1} BATH CIRCUITS ARE REQUIRED TO HAVE A 20 AMP | | | RECEPTACLE PER 210.11(C) (3), LOCATED PER 210.52(D), | | | AND BE GFI PROTECTED PER 210.8(A) (1). CIRCUIT #17 IN | | | THE MASTER BATH IS NOT RATED ON THE PANEL SCHEDULE, | | | THEY COULD BE ON 23 AS THAT CIRCUIT MEETS THE INTENT OF | | | THE EXCEPTION 210.11(C) (3). | | | | | | 2} THE "EXISTING BATH", SAME COMMENT AS ABOVE WITH | | | CIRCUITS19 AND 25. | | | | | | 3} PER 210.52(B) (1) & (2), THE CIRCUITS IN THE DINING | | | ROOM (# 27)MUST BE 20 AMP AS IT IS, BUT MUST BE | | | LABLED "DINING ROOM", NOT "GENERAL LIGHTING. ALSO | | | "SHALL HAVE NO OTHER OUTLETS" MEANS THE LIVING ROOM IS | | | IN VIOLATION BEING ON THE SAME CIRCUIT. | | | | | | 4}THE LIGHTING IN THE KITCHEN SHALL NOT BE ON A SMALL | | | APPLIANCE CIRCUIT, 210.52(B) (2). | | | | | | 5} CIRCUIT #6 IS LABLED "COOK TOP" ON THE SCHEDULE AND | | | "DOUBLE OVEN" ON THE PLAN, CORRELATE SAME. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|