2008-03-18 18:58:44 
  
  
 1)SIMONTON WINDOW PRODUCT APPROVAL DOES NOT COVER
 DH36 SIZE (53 1/8" X 74 1/4")
  
 2)SIMONTON SGD PRODUCT APPROVAL ONLY COVERS 3 LITE
 UNIT IN 107" X 80" SIZE THE UNIT BEING REPLACE IS
 12'-0"WIDE (144") BY 8'-0" TALL (96")
  
 3)PRODUCT APPROVALS AREA COMBINATION OF THE FLORIDA
 STATEWIDE PRODUCT APPROVAL AND MIAMI-DADE NOA'S AND
 NEITHER ONE MEETS THE SIZE REQUIREMENTS.
  
 4)PROVIDE ONLY THE APPROVALS THAT WILL MEET YOUR
 REQUIREMENTS FROM ONE ENTITY, THE CITY OF WEST PALM
 REQUIRES THE STATEWIDE APPROVALS WHEN AVAILABLE IF NOT
 MIAMI-DADE NOA'S WILL BE GIVEN LOCAL PRODUCT APPROVAL.
  
 5)IN EXISTING BUILDINGS WHERE MORE THAN 25% OF THE
 AGGREGATE AREA OF GLAZED OPENINGS ARE BEING REPLACED IN
 ANY 12 MONTH PERIOD IMPACT PROTECTION IS REQUIRED PER
 507.3 FBC EXISTING.
  
 6)SHUTTERAPPLICATIONS REQUIRE A KEY PLAN (WITH
 EGRESS SHOWN), SHUTTER SCHEDULE AND THE PRODUCT
 APPROVALS. APPROVAL DRAWINGS CAN BE MARKED FOR MOUNTING
 METHOD AND CONNECTION TYPE AND THE SCHEDULE FILLED OUT
 WITH ALL PERTINENT INFORMATION SPECIFIC TO THE SITE
 (TYPE OF CONSTRUCTION, MOUNTING CONNECTION METHOD,
 ANCHOR TYPE, SHUTTER SPAN (VERTICAL OR HORIZONTAL),
 ETC.) PLEASE SEE THE ATTACHED MEMO AND SCHEDULE.
  
 *******NOTE********
 SHUTTER INSTALLATION: FASTENERS FOR FILLED CELL
 BLOCK-WORK-CONTRACTOR CANNOT ASSUME THAT THERE IS A
 CONCRETE SUBSTRATE WHEN SELECTING FASTENERS (AND
 SPACING) UNLESS THEY CAN PROVIDE DOCUMENTATION TO
 VERIFY COMPRESSIVE STRENGTH OF 3,000 PSI, OR 3,500 PSI,
 ETC, AND THE REQUIRED FASTENER EMBEDMENT DEPTH,AS
 REQUIRED ON THE PRODUCT APPROVAL. IF DOCUMENTATION IS
 NOT PROVIDED THE SUBSTRATE SHALL BE CONSIDERED MASONRY
 AND THE O/C SPACING SHALL BE ADJUSTED ACCORDINGLY.
  
 7)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN
 THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING,
 THE NOTICE IS VOID, PLEASE HAVE RERECORDED
  