| 2008-03-18 18:58:44 | |
| | |
| | |
| | 1)SIMONTON WINDOW PRODUCT APPROVAL DOES NOT COVER |
| | DH36 SIZE (53 1/8" X 74 1/4") |
| | |
| | 2)SIMONTON SGD PRODUCT APPROVAL ONLY COVERS 3 LITE |
| | UNIT IN 107" X 80" SIZE THE UNIT BEING REPLACE IS |
| | 12'-0"WIDE (144") BY 8'-0" TALL (96") |
| | |
| | 3)PRODUCT APPROVALS AREA COMBINATION OF THE FLORIDA |
| | STATEWIDE PRODUCT APPROVAL AND MIAMI-DADE NOA'S AND |
| | NEITHER ONE MEETS THE SIZE REQUIREMENTS. |
| | |
| | 4)PROVIDE ONLY THE APPROVALS THAT WILL MEET YOUR |
| | REQUIREMENTS FROM ONE ENTITY, THE CITY OF WEST PALM |
| | REQUIRES THE STATEWIDE APPROVALS WHEN AVAILABLE IF NOT |
| | MIAMI-DADE NOA'S WILL BE GIVEN LOCAL PRODUCT APPROVAL. |
| | |
| | 5)IN EXISTING BUILDINGS WHERE MORE THAN 25% OF THE |
| | AGGREGATE AREA OF GLAZED OPENINGS ARE BEING REPLACED IN |
| | ANY 12 MONTH PERIOD IMPACT PROTECTION IS REQUIRED PER |
| | 507.3 FBC EXISTING. |
| | |
| | 6)SHUTTERAPPLICATIONS REQUIRE A KEY PLAN (WITH |
| | EGRESS SHOWN), SHUTTER SCHEDULE AND THE PRODUCT |
| | APPROVALS. APPROVAL DRAWINGS CAN BE MARKED FOR MOUNTING |
| | METHOD AND CONNECTION TYPE AND THE SCHEDULE FILLED OUT |
| | WITH ALL PERTINENT INFORMATION SPECIFIC TO THE SITE |
| | (TYPE OF CONSTRUCTION, MOUNTING CONNECTION METHOD, |
| | ANCHOR TYPE, SHUTTER SPAN (VERTICAL OR HORIZONTAL), |
| | ETC.) PLEASE SEE THE ATTACHED MEMO AND SCHEDULE. |
| | |
| | *******NOTE******** |
| | SHUTTER INSTALLATION: FASTENERS FOR FILLED CELL |
| | BLOCK-WORK-CONTRACTOR CANNOT ASSUME THAT THERE IS A |
| | CONCRETE SUBSTRATE WHEN SELECTING FASTENERS (AND |
| | SPACING) UNLESS THEY CAN PROVIDE DOCUMENTATION TO |
| | VERIFY COMPRESSIVE STRENGTH OF 3,000 PSI, OR 3,500 PSI, |
| | ETC, AND THE REQUIRED FASTENER EMBEDMENT DEPTH,AS |
| | REQUIRED ON THE PRODUCT APPROVAL. IF DOCUMENTATION IS |
| | NOT PROVIDED THE SUBSTRATE SHALL BE CONSIDERED MASONRY |
| | AND THE O/C SPACING SHALL BE ADJUSTED ACCORDINGLY. |
| | |
| | 7)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN |
| | THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING, |
| | THE NOTICE IS VOID, PLEASE HAVE RERECORDED |
| | |
| | BLDG PLAN REVIEW |