Plan Review Notes
Plan Review Notes For Permit 07080804
Permit Number 07080804
Review Stop P
Sequence Number 2
Notes
Date Text
2007-11-29 08:17:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-4 PLUMBING RISER DIAGRAM: THE TUB AND
 SHOWER REQUIRE TRAPS. PER *1002.1 FIXTURE TRAPS.
  
 2. THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEAL ACCEPTABLE TO THE BOARD PER F.A.C. 61G15-23.001
 AND F.S. 471.025.
 **NOTE: ONLY ONE SET OF PLANS WERE SEALED.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  