| Plan Review Notes For Permit 07080804 |
| Permit Number |
07080804 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-11-21 08:07:26 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THIS COMMENT IS FROM THE 9/5/07 REVIEW; | | | | | | 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). THAT CIRCUIT(S) IS NOT | | | SHOWN ON THE IN THE PANEL SCHEDULE. * THE CIRCUIUT IS | | | NOW SHOWN---AT 15 AMPS. PLEASE READ THE COMMENT THEN | | | REVIEW THE ARTICLE FOR CLARIFICATION. | | | | | | THESE ARE COMMENTS GENERATED FROM THE PLANS SUBMITTED | | | 11/15/07. | | | | | | 1} THE NOTE ON SHEET E-1 AT THE LOAD CALCULATIONS | | | INDICATES THE SERVICE IS 200 AMPS, THE FEEDERS ARE | | | INDICATED AS 1/0 WHICH PER 310.15(B)(6) IS RATED FOR | | | 175 AMPS. PLEASE FIELD VERIFY ACTUAL CONDITIONS AND | | | CORRECT THE PLAN. | | | | | | 2} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH | | | A SEAL ACCEPTABLE TO THE BOARD PER 61G15-23.001. ONLY | | | ONE SET OF PLANS ARE SEALED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|