| 2007-09-14 13:33:35 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING WITH 2006 REVISIONS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET A-3 FLOOR PLAN: CLEARLY IDENTIFY ALL PLUMBING |
| | FIXTURES IN THE MASTER BATH PER FBC-2004 CHAPTER 1, |
| | SECTION 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2. SHEET A-4 PLUMBING RISER DIAGRAM KITCHEN PLEASE |
| | CORRECT THE FOLLOWING: |
| | |
| | A} A SANITARY TEE IS NOT ALLOWED ON THE KITCHEN SINK |
| | FOR HORIZONTAL TO HORIZONTAL DRAINAGE PER FBC-2004 |
| | PLBG. TABLE 706.3. |
| | |
| | B} A DRAIN FOR THE DISHWASHER IS REQUIRED AND NEEDS TO |
| | BE INDICATED IN THE RESUBMITTED RISER DIAGRAM PER |
| | FBC-2004 PLBG. SECTION 802.1.6,DOMESTIC DISHWASHING |
| | MACHINES SHALL DISCHARGE INDIRECTLY THROUGH AN AIR GAP |
| | OR AIR BREAK INTO A STANDPIPE OR WASTE RECEPTOR IN |
| | ACCORDANCE WITH SECTION 802.2 OR DISCHARGE INTO A |
| | WYE-BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK |
| | OR THE DISHWASHER CONNECTION OF A FOOD WASTE GRINDER. |
| | |
| | 3. SHEET A-4 PLUMBING RISER DIAGRAM MASTER BATH PLEASE |
| | CORRECT THE FOLLOWING: |
| | |
| | A} A VENT IS REQUIRED FOR BOTH THE TUB AND SHOWER PER |
| | FBC-2004 PLBG. TABLE 906.1, THE 2 INCH TRAPS CAN NOT BE |
| | MORE THAN 6 FEET FROM THE VENT. THE TRAPS ARE NOW |
| | AROUND 8 FEET FROM THE VENT. |
| | |
| | B} A SANITARY TEE IS NOT ALLOWED ON THE LAVATORIES FOR |
| | HORIZONTAL TO HORIZONTAL DRAINAGE PER FBC-2004 PLBG. |
| | TABLE 706.3. |
| | |
| | C} SEND MANUFACTURER SPECIFICATION SHEET OF THE |
| | CIRCLED FITTING PER FBC-2004 CHAPTER 1, SECTION |
| | 106.1.1, INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK |
| | ON THE INDICATED PLAN SHEETS BY THIS PLANS EXAMINER FOR |
| | REFERENCE FOR THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |