| 2007-11-08 08:35:11 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE THE REVISED PLANS NOW SHOW SOME OF THE |
| | SAME ITEMS WHICH WERE NOT CODE COMPLIANT ON THE |
| | ORIGINAL REVIEW. THESE HAVE NO BEEN CORRECTED. |
| | ** THE ITEMS ON PLANS WHICH EXIST AND ARE NOT A LIFE |
| | SAFETY/FIRE HAZARD ARE NOT BEING CONSIDERED IN THIS |
| | REVIEW. |
| | |
| | |
| | 1) NOTE: PLEASE SEE SOME CIRCUITING IS STILL MISSING |
| | FROM PLANS AND REQUIRED CIRCUITS CAN NOT BE VERIFIED. |
| | FOR EXAMPLE: PLEASE SEE SMOKE ALARMS ARE MISSING |
| | CIRCUITING AND CIRCUITING MUST HAVE AFCI PROTECTION. |
| | 210.12 |
| | FOR EXAMPLE; MASTER BATH MISSING SPACING AND INDICATION |
| | OF GFI AT LAVATORY AREA. PLEASE KNOW THE GFI IS |
| | REQUIRED TO BE WITHIN 3FT IF SINK EDGE HOWEVER IT IS |
| | NOT PERMISSIBLE TO CROSS OVER A OPEN SINK TO REACH THE |
| | RECEPTACLE LOCATION. PLEASE SEE THAT AN ADDITIONAL GFI |
| | WILL BE REQUIRED OR RELOCATE THE ONE SHOWN. |
| | |
| | 2) NOTE: PLEASE SEE 210.8A6 AS ALL KITCHEN COUNTER |
| | SPACE RECEPTACLES ARE REQUIRED TO BE GFI/GFI PROTECTED. |
| | THE NOTE ON THE LOWER RIGHT HAND SIDE OF PLANS FOR GFI |
| | RECEPTACLES IS NOT ACCURATE AS THERE ARE MANY CHANGES |
| | IN THE CODES WHERE THESE NOTES ARE NOT. PLEASE ADJUST |
| | NOTE. |
| | 210.8 |
| | |
| | 3) NOTE: PLEASE SEE PANEL AND SERVICE SIZE AS PLANS |
| | STILL INDICATE 1/0 CONDUCTORS FOR 200AMP PANEL. PLANS |
| | ALSO SHOW 3/0, WHICHSIZE CONDUCTORS ARE INSTALLED. |
| | |
| | 4) NOTE: PLEASE SEE 424.3B AS MIN OCP FOR AHU 10KW HEAT |
| | IS 60AMPS. |
| | |
| | 5) NOTE: PLEASE SEE ELECTRICAL NOTE WHICH MENTIONS ALL |
| | WIRING TO BE #12 BETWEEN FIXTURES AND SWITCHES YET THE |
| | PANEL SCHEDULE SHOWS #14 ON MOST OF THESE. |
| | |
| | 6) NOTE: PLEASE SEE 410.8 AS THE LIGHTING IN CLOSET AS |
| | SHOWN IS NOT PERMITTED. THIS IS A FIRE HAZARD/LIFE |
| | SAFETY SITUATION. |
| | |
| | ** PLEASE SEE NEC 2005 AND LS CODE NFPA-101 2003 AS |
| | THERE ARE SEVERAL CHANGES WHICH ARE NEEDED. |
| | PLEASE REVISE PLANS FOR SCOPE OF WORK AND MINIMUM CODE |
| | COMPLIANCE. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |