Plan Review Notes For Permit 07080800
Permit Number 07080800
Review Stop E
Sequence Number 4
Notes
Date Text
2007-11-08 08:35:11** DENIED 3RD REVIEW **
  
 ** PLEASE SEE THE REVISED PLANS NOW SHOW SOME OF THE
 SAME ITEMS WHICH WERE NOT CODE COMPLIANT ON THE
 ORIGINAL REVIEW. THESE HAVE NO BEEN CORRECTED.
 ** THE ITEMS ON PLANS WHICH EXIST AND ARE NOT A LIFE
 SAFETY/FIRE HAZARD ARE NOT BEING CONSIDERED IN THIS
 REVIEW.
  
  
 1) NOTE: PLEASE SEE SOME CIRCUITING IS STILL MISSING
 FROM PLANS AND REQUIRED CIRCUITS CAN NOT BE VERIFIED.
 FOR EXAMPLE: PLEASE SEE SMOKE ALARMS ARE MISSING
 CIRCUITING AND CIRCUITING MUST HAVE AFCI PROTECTION.
 210.12
 FOR EXAMPLE; MASTER BATH MISSING SPACING AND INDICATION
 OF GFI AT LAVATORY AREA. PLEASE KNOW THE GFI IS
 REQUIRED TO BE WITHIN 3FT IF SINK EDGE HOWEVER IT IS
 NOT PERMISSIBLE TO CROSS OVER A OPEN SINK TO REACH THE
 RECEPTACLE LOCATION. PLEASE SEE THAT AN ADDITIONAL GFI
 WILL BE REQUIRED OR RELOCATE THE ONE SHOWN.
  
 2) NOTE: PLEASE SEE 210.8A6 AS ALL KITCHEN COUNTER
 SPACE RECEPTACLES ARE REQUIRED TO BE GFI/GFI PROTECTED.
 THE NOTE ON THE LOWER RIGHT HAND SIDE OF PLANS FOR GFI
 RECEPTACLES IS NOT ACCURATE AS THERE ARE MANY CHANGES
 IN THE CODES WHERE THESE NOTES ARE NOT. PLEASE ADJUST
 NOTE.
 210.8
  
 3) NOTE: PLEASE SEE PANEL AND SERVICE SIZE AS PLANS
 STILL INDICATE 1/0 CONDUCTORS FOR 200AMP PANEL. PLANS
 ALSO SHOW 3/0, WHICHSIZE CONDUCTORS ARE INSTALLED.
  
 4) NOTE: PLEASE SEE 424.3B AS MIN OCP FOR AHU 10KW HEAT
 IS 60AMPS.
  
 5) NOTE: PLEASE SEE ELECTRICAL NOTE WHICH MENTIONS ALL
 WIRING TO BE #12 BETWEEN FIXTURES AND SWITCHES YET THE
 PANEL SCHEDULE SHOWS #14 ON MOST OF THESE.
  
 6) NOTE: PLEASE SEE 410.8 AS THE LIGHTING IN CLOSET AS
 SHOWN IS NOT PERMITTED. THIS IS A FIRE HAZARD/LIFE
 SAFETY SITUATION.
  
 ** PLEASE SEE NEC 2005 AND LS CODE NFPA-101 2003 AS
 THERE ARE SEVERAL CHANGES WHICH ARE NEEDED.
 PLEASE REVISE PLANS FOR SCOPE OF WORK AND MINIMUM CODE
 COMPLIANCE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved