Plan Review Notes
Plan Review Notes For Permit 07080800
Permit Number 07080800
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-11 16:25:04** DENIED 2ND REVIEW**
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW NOTE DUE TO
 ADDITIONAL INFORMATION ONLY NOW SUBMITTED WHICH WAS NOT
 ON PREVIOUS PLANS.
  
 1) NOTE:SAME NOTE AS PREVIOUS REVIEW: THE ELECTRICAL
 PLANS STILL DO NOT CONTAIN THE REQUIRED RELEVANT CODES
 AS PREVIOUSLY GIVEN.
 **PREVIOUS REVIEW NOTE**
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE SMOKE ALARMS ARE NOW SHOWN AS NOTED
 ON PREVIOUS REVIEW NOTE #2, HOWEVER PLEASE SEE THE
 CIRCUITING FOR THESE ARE MISSING. PLEASE SEE PREVIOUS
 NOTE #7 ALSO AS ALL CIRCUITING WAS NOTED.
 PLEASE BE SURE TO SEE 210.12 FOR REQUIRED ARC FAULT
 PROTECTION.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE NEW ELECTRICAL FEEDERS ARE NOTED
 BOTH AS 1/0 AND 3/0. PLEASE KNOW IF THIS IS AN EXISTING
 200AMP MAIN AND PANEL AS NOTED ON PLANS THEN THE 1/0
 FEEDER CONDUCTOR SIZE IS NOT SUFFICIENT PER 310.16.
 PLEASE ADJUST.
  
 4) NOTE:PLEASE SEE NOTE #4 FROM PREVIOUS REVIEW: THIS
 IS THE SAME COMMENT.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE WATER HEATER UNDER THE NEW 2005 NEC IS
 REQUIRED TO BE SHOWN AT 125% IN LOAD CALCULATIONS.
 422.13
  
 5) NOTE: PLEASE SEE THAT THIS IS THE SAME NOTE FROM
 PREVIOUS REVIEW NOTE #5. THE PLANS STILL DO NOT
 INDICATE A RECEPTACLE FOR THE DISPOSAL?? PLEASE SEE
 NOTE WITH RESPECT TO BREAKERS TO THE SAME YOKE AS
 MENTIONED.
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE PLANS APPEAR TO BE MISSING THE RECEPTACLE
 LOCATION FOR THE DISPOSAL. PLEASE ALSO SEE THE 210.4B
 IF BOTH THE DISH/ DISP ARE BEING FED TO THE SAME YOKE
 WHICH WILL REQUIRE A 2-POLE BREAKER.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #8, AS THERE IS STILL
 REQUIRED GFI MISSING ALONG KITCHEN COUNTER-SPACE.
 ** PREVIOUS REVIEW NOTE #8**
 PLEASE SEE 210.52C1 FOR MISSING KITCHEN COUNTER SPACE
 GFI RECEPTACLES REQUIRED.
  
 7) NOTE:PLEASE SEE THE PREVIOUS REVIEW NOTE #9, AS
 THIS REMAINS THE EXACT SAME. THE PLAN NOTES WERE STILL
 NOT ADJUSTED OR CHANGED.
 ** PREVIOUS REVIEW NOTE #9**
 PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING KITCHEN
 COUNTER SPACE IS REQUIRED TO BE GFI OR GFI PROTECTED.
 THIS WAS CHANGED IN THE 1993 CODE. NOTE ON PLANS ONLY
 MENTIONS RECEPTACLES WITHIN 6FT OF SINKS. THIS IS FOR
 ALL OTHER AREAS.
  
 8) NOTE: PREVIOUS NOTE #11 REMAINS AS MENTIONED IN NOTE
 #2 ABOVE FOR ALL NEW OUTLETS IN BEDROOMS.
 PLEASE ALSO SEE THIS SECTION STILL APPLIES TO OTHER NEW
 CIRCUITS FOR BEDROOMS WHICH ARE NOT LISTED ON PANEL
 SCHEDULE WITH AFCI PROTECTION.
 ** PREVIOUS REVIEW NOTE #11**
 PLEASE SEE 210.12 FOR REQUIRED ARC FAULT PROTECTION
 FOR NEW OUTLETS IN BEDROOMS.
  
 9) NOTE: PLEASE KNOW AS THE PANEL SCHEDULE IS NOW
 SHOWN, PLEASE VERIFY THE OVER CURRENT PROTECTION NOW
 SHOWN FOR THE A/C. PLEASE SEE 424.3B AS THE LOAD IS
 SHOWN AT 10KW AND THE MINIMUM OVER CURRENT PROTECTION
 PER THIS SECTION REQUIRED 125 %(MIN).
 PLEASE VERIFY AND ADJUST AS NEEDED.
  
 10) NOTE: PLEASE SEE 680.71 AS NO GFI PROTECTION IS
 BEING SHOWN FOR THE NEW JACUZZI. PLEASE ALSO SEE THAT
 NO RECEPTACLE, DISCONNECT (IF NOT CORD AND PLUG) OR
 ACCESS LOCATION IS SHOWN ON PLANS.
  
 11) NOTE: PLEASE VERIFY NOTE WHICH MENTIONS CONDUCTOR
 INSULATION TO BE USED IS *TW*!!. PLEASE SEE 310.16 AS
 TW IS ONLY RATED AT THE 60DEGREE RATING.
 THIS IS ONLY BEING NOTED AS THE USE OF TW IS NOT A
 READILY AVAILABLE INSULATION AT THIS DAY AND TIME.
  
 12) NOTE: PLEASE VERIFY THE WATER HEATER LOCATION. THE
 PANEL SCHEDULE LIST THE WATER HEATER HOWEVER THE PLANS
 DO NOT SHOW THIS AS NEW OR EXISTING??
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS
 BEING GIVEN WITH RESPECT TO REPEAT COMMENTS. THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME.
  
 AS STATED ON PREVIOUS REVIEW IF THERE ARE ANY QUESTIONS
 OR COMMENTS TO PLEASE CALL TO GO OVER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]