| Date |
Text |
| 2007-10-11 16:25:04 | ** DENIED 2ND REVIEW** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED ALONG WITH NEW NOTE DUE TO |
| | ADDITIONAL INFORMATION ONLY NOW SUBMITTED WHICH WAS NOT |
| | ON PREVIOUS PLANS. |
| | |
| | 1) NOTE:SAME NOTE AS PREVIOUS REVIEW: THE ELECTRICAL |
| | PLANS STILL DO NOT CONTAIN THE REQUIRED RELEVANT CODES |
| | AS PREVIOUSLY GIVEN. |
| | **PREVIOUS REVIEW NOTE** |
| | PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE |
| | THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC |
| | FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE |
| | ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL |
| | TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: PLEASE SEE SMOKE ALARMS ARE NOW SHOWN AS NOTED |
| | ON PREVIOUS REVIEW NOTE #2, HOWEVER PLEASE SEE THE |
| | CIRCUITING FOR THESE ARE MISSING. PLEASE SEE PREVIOUS |
| | NOTE #7 ALSO AS ALL CIRCUITING WAS NOTED. |
| | PLEASE BE SURE TO SEE 210.12 FOR REQUIRED ARC FAULT |
| | PROTECTION. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE NEW ELECTRICAL FEEDERS ARE NOTED |
| | BOTH AS 1/0 AND 3/0. PLEASE KNOW IF THIS IS AN EXISTING |
| | 200AMP MAIN AND PANEL AS NOTED ON PLANS THEN THE 1/0 |
| | FEEDER CONDUCTOR SIZE IS NOT SUFFICIENT PER 310.16. |
| | PLEASE ADJUST. |
| | |
| | 4) NOTE:PLEASE SEE NOTE #4 FROM PREVIOUS REVIEW: THIS |
| | IS THE SAME COMMENT. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE WATER HEATER UNDER THE NEW 2005 NEC IS |
| | REQUIRED TO BE SHOWN AT 125% IN LOAD CALCULATIONS. |
| | 422.13 |
| | |
| | 5) NOTE: PLEASE SEE THAT THIS IS THE SAME NOTE FROM |
| | PREVIOUS REVIEW NOTE #5. THE PLANS STILL DO NOT |
| | INDICATE A RECEPTACLE FOR THE DISPOSAL?? PLEASE SEE |
| | NOTE WITH RESPECT TO BREAKERS TO THE SAME YOKE AS |
| | MENTIONED. |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE PLANS APPEAR TO BE MISSING THE RECEPTACLE |
| | LOCATION FOR THE DISPOSAL. PLEASE ALSO SEE THE 210.4B |
| | IF BOTH THE DISH/ DISP ARE BEING FED TO THE SAME YOKE |
| | WHICH WILL REQUIRE A 2-POLE BREAKER. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTE #8, AS THERE IS STILL |
| | REQUIRED GFI MISSING ALONG KITCHEN COUNTER-SPACE. |
| | ** PREVIOUS REVIEW NOTE #8** |
| | PLEASE SEE 210.52C1 FOR MISSING KITCHEN COUNTER SPACE |
| | GFI RECEPTACLES REQUIRED. |
| | |
| | 7) NOTE:PLEASE SEE THE PREVIOUS REVIEW NOTE #9, AS |
| | THIS REMAINS THE EXACT SAME. THE PLAN NOTES WERE STILL |
| | NOT ADJUSTED OR CHANGED. |
| | ** PREVIOUS REVIEW NOTE #9** |
| | PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING KITCHEN |
| | COUNTER SPACE IS REQUIRED TO BE GFI OR GFI PROTECTED. |
| | THIS WAS CHANGED IN THE 1993 CODE. NOTE ON PLANS ONLY |
| | MENTIONS RECEPTACLES WITHIN 6FT OF SINKS. THIS IS FOR |
| | ALL OTHER AREAS. |
| | |
| | 8) NOTE: PREVIOUS NOTE #11 REMAINS AS MENTIONED IN NOTE |
| | #2 ABOVE FOR ALL NEW OUTLETS IN BEDROOMS. |
| | PLEASE ALSO SEE THIS SECTION STILL APPLIES TO OTHER NEW |
| | CIRCUITS FOR BEDROOMS WHICH ARE NOT LISTED ON PANEL |
| | SCHEDULE WITH AFCI PROTECTION. |
| | ** PREVIOUS REVIEW NOTE #11** |
| | PLEASE SEE 210.12 FOR REQUIRED ARC FAULT PROTECTION |
| | FOR NEW OUTLETS IN BEDROOMS. |
| | |
| | 9) NOTE: PLEASE KNOW AS THE PANEL SCHEDULE IS NOW |
| | SHOWN, PLEASE VERIFY THE OVER CURRENT PROTECTION NOW |
| | SHOWN FOR THE A/C. PLEASE SEE 424.3B AS THE LOAD IS |
| | SHOWN AT 10KW AND THE MINIMUM OVER CURRENT PROTECTION |
| | PER THIS SECTION REQUIRED 125 %(MIN). |
| | PLEASE VERIFY AND ADJUST AS NEEDED. |
| | |
| | 10) NOTE: PLEASE SEE 680.71 AS NO GFI PROTECTION IS |
| | BEING SHOWN FOR THE NEW JACUZZI. PLEASE ALSO SEE THAT |
| | NO RECEPTACLE, DISCONNECT (IF NOT CORD AND PLUG) OR |
| | ACCESS LOCATION IS SHOWN ON PLANS. |
| | |
| | 11) NOTE: PLEASE VERIFY NOTE WHICH MENTIONS CONDUCTOR |
| | INSULATION TO BE USED IS *TW*!!. PLEASE SEE 310.16 AS |
| | TW IS ONLY RATED AT THE 60DEGREE RATING. |
| | THIS IS ONLY BEING NOTED AS THE USE OF TW IS NOT A |
| | READILY AVAILABLE INSULATION AT THIS DAY AND TIME. |
| | |
| | 12) NOTE: PLEASE VERIFY THE WATER HEATER LOCATION. THE |
| | PANEL SCHEDULE LIST THE WATER HEATER HOWEVER THE PLANS |
| | DO NOT SHOW THIS AS NEW OR EXISTING?? |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS |
| | BEING GIVEN WITH RESPECT TO REPEAT COMMENTS. THIS IS |
| | ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | AS STATED ON PREVIOUS REVIEW IF THERE ARE ANY QUESTIONS |
| | OR COMMENTS TO PLEASE CALL TO GO OVER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |