Plan Review Notes
Plan Review Notes For Permit 07080800
Permit Number 07080800
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-20 12:47:13*****DENIED*****
  
  
 1.ON SHEET A-1 UNDER CODE SUMMARY,INDICATE 2003
 EDITION OF NFPA 101.
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 3.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER ACCESS TO OR EGRESS FROM THE FLOOR OR THE
 BUILDING.
  
 4.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5.IT IS SHOWN ON SHEET E-1 OF SMOKE DETECTORS (SD) IN
 THE DWELLING UNIT.AMEND TO SHOW THESE DEVICES AS
 SMOKE ALARMS (SA).PLEASE BE ADVISED THAT SMOKE
 DETECTORS ARE TIED INTO THE BUILDING'S FIRE ALARM
 SYSTEM, WHEREAS SMOKE ALARMS WHEN ACTIVATED ALERT THE
 THE OCCUPANTS OF THE INDIVIDUAL DWELLING UNIT.
  
 6.THE CORRECT DWELLING UNIT NUMBER SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.PLEASE SEE
 THAT OUR COMPUTER SYSTEM (AS WELL AS YOUR APPLICATION)
 HAS THIS SPACE AS 2402 BUT IS SHOWN AS 24B ON THE
 SUBMITTED PLANS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW