| Notes |
| Date |
Text |
| 2007-09-20 12:47:13 | *****DENIED***** | | | | | | | | | 1.ON SHEET A-1 UNDER CODE SUMMARY,INDICATE 2003 | | | EDITION OF NFPA 101. | | | | | | 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241. | | | | | | 3.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE | | | OR HINDER ACCESS TO OR EGRESS FROM THE FLOOR OR THE | | | BUILDING. | | | | | | 4.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 5.IT IS SHOWN ON SHEET E-1 OF SMOKE DETECTORS (SD) IN | | | THE DWELLING UNIT.AMEND TO SHOW THESE DEVICES AS | | | SMOKE ALARMS (SA).PLEASE BE ADVISED THAT SMOKE | | | DETECTORS ARE TIED INTO THE BUILDING'S FIRE ALARM | | | SYSTEM, WHEREAS SMOKE ALARMS WHEN ACTIVATED ALERT THE | | | THE OCCUPANTS OF THE INDIVIDUAL DWELLING UNIT. | | | | | | 6.THE CORRECT DWELLING UNIT NUMBER SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.PLEASE SEE | | | THAT OUR COMPUTER SYSTEM (AS WELL AS YOUR APPLICATION) | | | HAS THIS SPACE AS 2402 BUT IS SHOWN AS 24B ON THE | | | SUBMITTED PLANS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|