Plan Review Notes
Plan Review Notes For Permit 07080800
Permit Number 07080800
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-08 17:22:082007-09-08 17:22:08
  
 ** DENIED **
  
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE
 INDICATE SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS
 THESE AS SMOKE DETECTORS.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 3) NOTE: PLEASE COMPLETE PANEL SCHEDULE WITH THE
 CONDUCTOR SIZES PER 240.4, 310.16, AND 408.4.
  
 4) NOTE: PLEASE SEE THE WATER HEATER UNDER THE NEW 2005
 NEC IS REQUIRED TO BE SHOWN AT 125% IN LOAD
 CALCULATIONS.
 422.13
  
 5) NOTE: PLEASE SEE PLANS APPEAR TO BE MISSING THE
 RECEPTACLE LOCATION FOR THE DISPOSAL. PLEASE ALSO SEE
 THE 210.4B IF BOTH THE DISH/ DISP ARE BEING FED TO THE
 SAME YOKE WHICH WILL REQUIRE A 2-POLE BREAKER.
  
 6) NOTE: PLEASE BE SURE TO STATE THE TYPE OF RECESSED
 LIGHTING FIXTURE TO BE USED FBC 13-606.1.ABC.1.2.4.
 THIS IS TO ALLEVIATE THE AIR MOVEMENT FROM CONDITIONED
 SPACE ETC.
  
 7) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS FOR
 NEW ELECTRICAL AS SHOWN.
 PLEASE BE SURE TO CORRELATE THIS WITH A PANEL SCHEDULE
 TO BE SUBMITTED SHOWING NEW AND EXISTING CIRCUITS.
 PLEASE KNOW AT THIS TIME THE MINIMUM REQUIRED CIRCUITS
 UNDER THE NEC ARE NOT SHOWN.PLEASE KNOW THAT THE PLANS
 NEED TO LABEL AND PROVIDE ROOM AND AREA DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE PANEL SCHEDULES SHOWING
 ALL ROOMS AND AREAS IN WHICH CIRCUITS FEED WILL BE
 REQUIRED FOR EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN
 FROM COMMENTARY IN THE CODE WHICH STATES THE USE OF
 *GEN LT* ETC IS NOT ACCEPTABLE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 8) NOTE: PLEASE SEE 210.52C1 FOR MISSING KITCHEN
 COUNTER SPACE GFI RECEPTACLES REQUIRED.
  
 9) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE IS REQUIRED TO BE GFI OR GFI
 PROTECTED. THIS WAS CHANGED IN THE 1993 CODE. NOTE ON
 PLANS ONLY MENTIONS RECEPTACLES WITHIN 6FT OF SINKS.
 THIS IS FOR ALL OTHER AREAS.
  
 10) NOTE: PLEASE SEE SEVERAL SECTIONS OF THE NEC FOR
 MINIMUM LOADS AND CIRCUITS FOR SMALL APPLIANCE,
 DINING/BREAKFAST AREAS, DISHWASHER, DISPOSAL, ETC ETC.
 PLEASE INCLUDE ALL OF THESE MINIMUM CIRCUITS AND LOADS
 ON THE PANEL SCHEDULE AS NOTED ABOVE WITH CONDUCTOR
 SIZES.
 PLEASE SUBMIT LOAD CALCULATIONS WITH NEW AND EXISTING
 LOADS.
 PLEASE SEE NEC 220.53, 210.52B1, 210.11C1, 210.11C2,
 ETC.
  
 11) NOTE: PLEASE SEE 210.12 FOR REQUIRED ARC FAULT
 PROTECTION FOR NEW OUTLETS IN BEDROOMS.
  
 12) NOTE: PLEASE SEE 210.11C3,FOR MINIMUM 20AMP AND
 #12 FOR BATH(S) CIRCUIT(S).
  
 13) NOTE: PLEASE SEE MISSING LICENSE NUMBER INFORMATION
 FOR ARCHITECTURAL AND DESIGN FIRM AS LISTED ON TITLE
 BLOCKS PER FLORIDA ADMINISTRATIVE CODE 61G1-16.004,
 FLORIDA STATUTES 481.023.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]