| Plan Review Notes For Permit 07080761 |
| Permit Number |
07080761 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-05 08:01:24 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 | | | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH | | | THE FOLLOWING: | | | | | | 1} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS | | | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING | | | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE | | | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE | | | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE | | | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE | | | COMPLIANCE ON THE PLAN. | | | | | | 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). THE MASTER BATH HAS A | | | SECOND SINK AND MUST HAVE A RECEPTACLE ADDED PER | | | 210.52(D), OR MOVE THEW EXISTING ONE TO COMPLY WITH THE | | | 3' MAXIMUM SPACE REQUIREMENT. | | | | | | 3} PER SECTION 608 AND 608.3 EXISTING BUILDING CODE, | | | SHOW REQUIRED RECEPTACLE SPACING IN THOSE AREAS. 210.52 | | | 2005 NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|