2007-09-02 17:45:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)SHUTTER CONNECTION MOUNTING TYPE SHOULD BE A
 THROUGH L (CORRELATES WITH ANCHOR SCHEDULE).
  
 2.)SEE SHEET 14.1 1/2" EDGE DISTANCE NOT ALLOWED.
  
 3.)YOU'VE DECLARED A BUILDING HEIGHT OF 30'.IT
 APPEARS TO BE AT LEAST A 5 STORY BUILDING.PLEASE
 ADDRESS.ENGINEERING MAY BE REQUIRED.
  
 4.)DESIGN PRESSURES TOO LOW, FBC TABLE 1609.6.2.1(2).
 THIS IS EXPOSURE C.REVISE.
  