2008-05-01 12:25:59 
  
  
  
 **DENIED 3RD REVIEW**
  
 THE FOLLOWING ARE COMMENTS FROM PREVIOUS REVIEWS THAT
 HAVE NOT BEEN CORRECTED FOR CODE COMPLIANCE.
  
 2}THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.*THE VALUE
 WAS ADJUSTED ON THE APPLICATION BUT NOT AT PERMIT
 SPECIALISTS DESK, AND THE DIFFERENCE HAS NOT BEEN PAID.
 SEE ATTACHED STATEMENT.
  
 6} 13-415.1.ABC1.1 WAS NOT COMPLIED WITH. SEE
 13-415.1.ABC.1.1 AUTOMATIC LIGHTING SHUTOFF.
  
 7} ENERGY CALCULATIONS WERE NOT SUBMITTED PER 13-101
 FBCTHE LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2B THAT ARE ON SHEET ELEC ARE COMPLIANT FOR
 METHOD C.
  
 9} THE LIGHTING LEVELS INDICATED FOR THE STAIRS IS NOT
 IN COMPLIANCE WITH 7.8.1.3 (1).NFPA 101 IS
 10FT-CANDLE.
  
 NEW COMMENTS GENERATED FROM THE REVISED PANEL
 SCHEDULE:
  
 1} THE CIRCUIT NUMBERS 2,4 AND 6,8 FOR THE DISCONNECTS
 DO NOT CORRELATE WITH THE PANEL SCHEDULE.IF THE
 DISCONNECTS ARE FOR THE CONDENSING UNITS, THE THIRD ONE
 IS NOT LOCATED ON THE PLAN. SHOW THE LOCATION OF THE
 A/C EQUIPMENT ON THE PLAN. ALSO SHOW COMPLIANCE WITH
 THE REQUIRED DISCONNECT PER 440.14,RECEPTACLE PER
 210.63.
  