| 2008-05-01 12:25:59 | |
| | |
| | |
| | |
| | **DENIED 3RD REVIEW** |
| | |
| | THE FOLLOWING ARE COMMENTS FROM PREVIOUS REVIEWS THAT |
| | HAVE NOT BEEN CORRECTED FOR CODE COMPLIANCE. |
| | |
| | 2}THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS |
| | AMENDED. |
| | |
| | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED |
| | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. |
| | 108.1 FBC. |
| | |
| | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY |
| | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.*THE VALUE |
| | WAS ADJUSTED ON THE APPLICATION BUT NOT AT PERMIT |
| | SPECIALISTS DESK, AND THE DIFFERENCE HAS NOT BEEN PAID. |
| | SEE ATTACHED STATEMENT. |
| | |
| | 6} 13-415.1.ABC1.1 WAS NOT COMPLIED WITH. SEE |
| | 13-415.1.ABC.1.1 AUTOMATIC LIGHTING SHUTOFF. |
| | |
| | 7} ENERGY CALCULATIONS WERE NOT SUBMITTED PER 13-101 |
| | FBCTHE LIGHTING PERFORMANCE CALCULATIONS PER |
| | 13-415.2B THAT ARE ON SHEET ELEC ARE COMPLIANT FOR |
| | METHOD C. |
| | |
| | 9} THE LIGHTING LEVELS INDICATED FOR THE STAIRS IS NOT |
| | IN COMPLIANCE WITH 7.8.1.3 (1).NFPA 101 IS |
| | 10FT-CANDLE. |
| | |
| | NEW COMMENTS GENERATED FROM THE REVISED PANEL |
| | SCHEDULE: |
| | |
| | 1} THE CIRCUIT NUMBERS 2,4 AND 6,8 FOR THE DISCONNECTS |
| | DO NOT CORRELATE WITH THE PANEL SCHEDULE.IF THE |
| | DISCONNECTS ARE FOR THE CONDENSING UNITS, THE THIRD ONE |
| | IS NOT LOCATED ON THE PLAN. SHOW THE LOCATION OF THE |
| | A/C EQUIPMENT ON THE PLAN. ALSO SHOW COMPLIANCE WITH |
| | THE REQUIRED DISCONNECT PER 440.14,RECEPTACLE PER |
| | 210.63. |
| | |