Plan Review Notes
Plan Review Notes For Permit 07080729
Permit Number 07080729
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-04 09:46:49** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 ** COMMENTS BELOW ARE FROM PREVIOUS REVIEW WITH A NOTE
 IN FRONT OF NOTE WHETHER OR NOT IT WAS ADDRESSED.
  
 1) NOTE:NO, PLEASE SEE NO SPECIFIC CODES AS REQUIRED
 WERE STATED OR SHOWN ON PLANS.
  
 *** PREVIOUS REVIEW NOTE ***
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72(IF AN FA SYSTEM IS IN BUILDING)
 2003 NFPA-101
  
 2) NOTE: NO, VALUE FOR SCOPE OF WORK ON PLANS DID NOT
 CHANGE. VALUE STILL SHOWN AS $2500 AND A VALUE MAY BE
 ASSESSED USING THE ADOPTED GUIDES INTO THE FBC IF AN
 APPROPRIATE VALUE IS NOT ADJUSTED.
  
 **PREVIOUS REVIEW NOTE ***
 PLEASE SEE THE VALUE AS SUBMITTED ON PERMIT
 APPLICATION BASED ON THE SCOPE OF WORK ON PLANS AND
 WHICH WILL BE REQUIRED IS EXTREMELY LOW.
 PLEASE SEE FBC 108.3 AS THE VALUE SHALL INCLUDE ALL
 LABOR, MATERIALS, COST OF
 DESIGN/ARCHITECTURAL/ENGINEERING SERVICES AND COST.
 THIS DOES NOT MATTER IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
 PLEASE KNOW THE VALUE WILL BE REQUIRED TO BE ADJUSTED
 OR A VALUE MAY BE APPLIED BY THIS OFFICE USING THE
 MINIMUM STANDARDS ADOPTED INTO AND BY THE FLORIDA
 BUILDING CODE AND ADOPTED STANDARDS.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE(S).
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: NO, PLEASE SEE NO DEVICES ARE SHOWN FOR NEW TO
 BE INSTALLED FOR COMPLIANCE WITH FBC AND CHAPTER 13.
  
 ** PREVIOUS REVIEW NOTE ***
 PLEASE SUBMIT PLANS WITH COMPLIANCE FOR FBC CHAPTER 13
 FOR LIGHTING CONTROLS. PLEASE SEE 13-415.1.ABC.1.1,
 .1.2.
 PLEASE INDICATE THE TYPE OF DEVICES OR SYSTEM WHICH
 WILL BE PROPOSED.
 PLEASE INCLUDE MAXIMUM TIMES ON ANY OVER RIDE DEVICES
 OR OCCUPANCY SENSOR DEVICES ETC.
 AS NO INFORMATION OR ITEMS WERE SUBMITTED FOR REVIEW, A
 FULL REVIEW FOR CODE COMPLIANCE COULD NOT BE DONE AT
 THIS TIME.
  
 7) NOTE:NO, PLEASE SEE NO LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW AREAS WERE SUBMITTED. PLEASE SEE
 13-415.2 OF THE FBC. FIXTURE LEGEND WAS SUBMITTED AS
 REQUESTED FROM PREVIOUS NOTE.
  
 *** PREVIOUS REVIEW NOTE ***
 PLEASE SUBMIT AND COMPLETE A FIXTURE LEGEND. PLEASE
 INCLUDE THE LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE KNOW IF SPACE IS NOW BEING AIR CONDITIONED,
 PLEASE SUBMIT ENERGY CALCULATIONS.
 13-101, 13-103.1.1.1, 13-415.1.B, 13-415.1.C, 13-415.2
 AS NO INFORMATION WAS SUBMITTED FOR MINIMUM CODE
 COMPLIANCE A REVIEW OF THESE ITEMS COULD NOT BE DONE.
  
 8) NOTE: OK.
  
 9) NOTE:NO, PLEASE SEE PLANS INDICATE THE UPPER
 MEZZANINE HOWEVER NO LEVELS FOR EGRESS LIGHTING WAS
 INDICATED FOR STAIRS, CORRIDOR.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2 , 7.8, 7.9. FAC
 61G15-33.004.
  
 ** PREVIOUS REVIEW NOTE **
 PLANS DO NOT INDICATE THE UPPER MEZZANINE LEVEL AS
 NOTED.
 PLANS DO NOT INDICATE ANY EMERGENCY LIGHTING FIXTURES
 NEEDED FOR MINIMUM EGRESS.
 PLEASE SEE THE STAIRS ALONE NEEDS LIGHTING LEVELS UNDER
 NORMAL AND EMERGENCY TO MEET THE LEVELS AS STATED IN
 THE LIFE SAFETY CODE 101, 7.8.1.3, AND 7.9.2.2. PLEASE
 SUBMIT THE PHOTO-METRIC LEVELS FOR STAIRS. PLEASE
 INDICATE THE EMERGENCY LIGHTING FIXTURES AT OTHER
 LOCATIONS TO MEET 1FT CANDLE MINIMUM.
 ** PLEASE BE SURE TO SEE NEC 700.12F FOR CIRCUITING OF
 THESE FIXTURES.
  
 10) NOTE: NO, LOADSARE SHOWN ON PANEL SCHEDULE
 HOWEVER PLEASE INDICATE WHERE THE CONTINUOUS LOADS AT
 125% ARE SHOWN??
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE LOAD CALCULATIONS WHICH INDICATE ALL
 CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]