| 2007-09-08 20:12:01 | 2007-09-08 20:12:01 |
| | |
| | ** DENIED ** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72(IF AN FA SYSTEM IS IN BUILDING) |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE AS SUBMITTED ON PERMIT |
| | APPLICATION BASED ON THE SCOPE OF WORK ON PLANS AND |
| | WHICH WILL BE REQUIRED IS EXTREMELY LOW. |
| | PLEASE SEE FBC 108.3 AS THE VALUE SHALL INCLUDE ALL |
| | LABOR, MATERIALS, COST OF |
| | DESIGN/ARCHITECTURAL/ENGINEERING SERVICES AND COST. |
| | THIS DOES NOT MATTER IF ANY OF THESE ITEMS ARE OWNER |
| | SUPPLIED. |
| | PLEASE KNOW THE VALUE WILL BE REQUIRED TO BE ADJUSTED |
| | OR A VALUE MAY BE APPLIED BY THIS OFFICE USING THE |
| | MINIMUM STANDARDS ADOPTED INTO AND BY THE FLORIDA |
| | BUILDING CODE AND ADOPTED STANDARDS. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE(S). |
| | |
| | 3) NOTE: PLEASE SEE THE PERMIT APPLICATIONS AS |
| | SUBMITTED. THE CGC APPLICATION STATES WORK AT 5407 AND |
| | THE ELECTRICAL CONTRACTOR HAS 5701 ON APPLICATION. |
| | PLEASE BE SURE TO COORDINATE. |
| | |
| | 4) NOTE: PLEASE SEE THE SUITE/UNIT NUMBER IS TO BE |
| | INCLUDED ON PLANS IN THE TITLE BLOCKS. |
| | FAC 61G15-23.002, 61G1-16.004, FBC 106.1.2, 106.1, |
| | 110.1.2. |
| | |
| | 5) NOTE: PLEASE SEE THE PLANS AS SUBMITTED DO NOT |
| | CONTAIN ANY DESIGN PROFESSIONAL PRINTED, SIGNED, DATED |
| | OR SEALED ON PLANS. |
| | PLEASE SEE THAT PLANS ARE REQUIRED TO BE DONE BY A |
| | DESIGN PROFESSIONAL UNDER FS 471,481,489 (WHERE |
| | PERMITTED). |
| | |
| | 6) NOTE: PLEASE SUBMIT PLANS WITH COMPLIANCE FOR FBC |
| | CHAPTER 13 FOR LIGHTING CONTROLS. PLEASE SEE |
| | 13-415.1.ABC.1.1, .1.2. |
| | PLEASE INDICATE THE TYPE OF DEVICES OR SYSTEM WHICH |
| | WILL BE PROPOSED. |
| | PLEASE INCLUDE MAXIMUM TIMES ON ANY OVER RIDE DEVICES |
| | OR OCCUPANCY SENSOR DEVICES ETC. |
| | AS NOT INFORMATION OR ITEMS WERE SUBMITTED FOR REVIEW, |
| | A FULL REVIEW FOR CODE COMPLIANCE COULD NOT BE DONE AT |
| | THIS TIME. |
| | |
| | 7) NOTE: PLEASE SUBMIT AND COMPLETE A FIXTURE LEGEND. |
| | PLEASE INCLUDE THE LIGHTING PERFORMANCE CALCULATIONS |
| | PER 13-415.2. |
| | PLEASE KNOW IF SPACE IS NOW BEING AIR CONDITIONED, |
| | PLEASE SUBMIT ENERGY CALCULATIONS. |
| | 13-101, 13-103.1.1.1, 13-415.1.B, 13-415.1.C, 13-415.2 |
| | AS NO INFORMATION WAS SUBMITTED FOR MINIMUM CODE |
| | COMPLIANCE A REVIEW OF THESE ITEMS COULD NOT BE DONE. |
| | |
| | 8) NOTE: PLEASE SEE THE SPACE DOES NOT STATE USE AND |
| | WHAT ITEMS WILL BE STORED AND/OR WHAT WAREHOUSE WILL BE |
| | USED FOR. |
| | PLEASE STATE USE AND OCCUPANCY. |
| | PLEASE BE AWARE OF ANY LOCATIONS WHICH MAY INVOKE |
| | SECTIONS OF THE LIFE SAFETY CODE, BUILDING CODE, |
| | ELECTRICAL CODE AND OTHER POSSIBLE CODES FOR WIRING, |
| | CONSTRUCTION OF WALLS ETC. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLANS DO NOT INDICATE THE UPPER MEZZANINE |
| | LEVEL AS NOTED. |
| | PLANS DO NOT INDICATE ANY EMERGENCY LIGHTING FIXTURES |
| | NEEDED FOR MINIMUM EGRESS. |
| | PLEASE SEE THE STAIRS ALONE NEEDS LIGHTING LEVELS UNDER |
| | NORMAL AND EMERGENCY TO MEET THE LEVELS AS STATED IN |
| | THE LIFE SAFETY CODE 101, 7.8.1.3, AND 7.9.2.2. PLEASE |
| | SUBMIT THE PHOTO-METRIC LEVELS FOR STAIRS. PLEASE |
| | INDICATE THE EMERGENCY LIGHTING FIXTURES AT OTHER |
| | LOCATIONS TO MEET 1FT CANDLE MINIMUM. |
| | ** PLEASE BE SURE TO SEE NEC 700.12F FOR CIRCUITING OF |
| | THESE FIXTURES. |
| | |
| | 10) NOTE: PLEASE SUBMIT THE LOAD CALCULATIONS WHICH |
| | INDICATE ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 ETC. |
| | |
| | ** PLEASE KNOW ONE SET OF PLANS MAY BE RETAINED BY THIS |
| | OFFICE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |