Plan Review Notes
Plan Review Notes For Permit 07080729
Permit Number 07080729
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-08 20:12:012007-09-08 20:12:01
  
 ** DENIED **
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72(IF AN FA SYSTEM IS IN BUILDING)
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE VALUE AS SUBMITTED ON PERMIT
 APPLICATION BASED ON THE SCOPE OF WORK ON PLANS AND
 WHICH WILL BE REQUIRED IS EXTREMELY LOW.
 PLEASE SEE FBC 108.3 AS THE VALUE SHALL INCLUDE ALL
 LABOR, MATERIALS, COST OF
 DESIGN/ARCHITECTURAL/ENGINEERING SERVICES AND COST.
 THIS DOES NOT MATTER IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
 PLEASE KNOW THE VALUE WILL BE REQUIRED TO BE ADJUSTED
 OR A VALUE MAY BE APPLIED BY THIS OFFICE USING THE
 MINIMUM STANDARDS ADOPTED INTO AND BY THE FLORIDA
 BUILDING CODE AND ADOPTED STANDARDS.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE(S).
  
 3) NOTE: PLEASE SEE THE PERMIT APPLICATIONS AS
 SUBMITTED. THE CGC APPLICATION STATES WORK AT 5407 AND
 THE ELECTRICAL CONTRACTOR HAS 5701 ON APPLICATION.
 PLEASE BE SURE TO COORDINATE.
  
 4) NOTE: PLEASE SEE THE SUITE/UNIT NUMBER IS TO BE
 INCLUDED ON PLANS IN THE TITLE BLOCKS.
 FAC 61G15-23.002, 61G1-16.004, FBC 106.1.2, 106.1,
 110.1.2.
  
 5) NOTE: PLEASE SEE THE PLANS AS SUBMITTED DO NOT
 CONTAIN ANY DESIGN PROFESSIONAL PRINTED, SIGNED, DATED
 OR SEALED ON PLANS.
 PLEASE SEE THAT PLANS ARE REQUIRED TO BE DONE BY A
 DESIGN PROFESSIONAL UNDER FS 471,481,489 (WHERE
 PERMITTED).
  
 6) NOTE: PLEASE SUBMIT PLANS WITH COMPLIANCE FOR FBC
 CHAPTER 13 FOR LIGHTING CONTROLS. PLEASE SEE
 13-415.1.ABC.1.1, .1.2.
 PLEASE INDICATE THE TYPE OF DEVICES OR SYSTEM WHICH
 WILL BE PROPOSED.
 PLEASE INCLUDE MAXIMUM TIMES ON ANY OVER RIDE DEVICES
 OR OCCUPANCY SENSOR DEVICES ETC.
 AS NOT INFORMATION OR ITEMS WERE SUBMITTED FOR REVIEW,
 A FULL REVIEW FOR CODE COMPLIANCE COULD NOT BE DONE AT
 THIS TIME.
  
 7) NOTE: PLEASE SUBMIT AND COMPLETE A FIXTURE LEGEND.
 PLEASE INCLUDE THE LIGHTING PERFORMANCE CALCULATIONS
 PER 13-415.2.
 PLEASE KNOW IF SPACE IS NOW BEING AIR CONDITIONED,
 PLEASE SUBMIT ENERGY CALCULATIONS.
 13-101, 13-103.1.1.1, 13-415.1.B, 13-415.1.C, 13-415.2
 AS NO INFORMATION WAS SUBMITTED FOR MINIMUM CODE
 COMPLIANCE A REVIEW OF THESE ITEMS COULD NOT BE DONE.
  
 8) NOTE: PLEASE SEE THE SPACE DOES NOT STATE USE AND
 WHAT ITEMS WILL BE STORED AND/OR WHAT WAREHOUSE WILL BE
 USED FOR.
 PLEASE STATE USE AND OCCUPANCY.
 PLEASE BE AWARE OF ANY LOCATIONS WHICH MAY INVOKE
 SECTIONS OF THE LIFE SAFETY CODE, BUILDING CODE,
 ELECTRICAL CODE AND OTHER POSSIBLE CODES FOR WIRING,
 CONSTRUCTION OF WALLS ETC.
 FBC 106.1.2
  
 9) NOTE: PLANS DO NOT INDICATE THE UPPER MEZZANINE
 LEVEL AS NOTED.
 PLANS DO NOT INDICATE ANY EMERGENCY LIGHTING FIXTURES
 NEEDED FOR MINIMUM EGRESS.
 PLEASE SEE THE STAIRS ALONE NEEDS LIGHTING LEVELS UNDER
 NORMAL AND EMERGENCY TO MEET THE LEVELS AS STATED IN
 THE LIFE SAFETY CODE 101, 7.8.1.3, AND 7.9.2.2. PLEASE
 SUBMIT THE PHOTO-METRIC LEVELS FOR STAIRS. PLEASE
 INDICATE THE EMERGENCY LIGHTING FIXTURES AT OTHER
 LOCATIONS TO MEET 1FT CANDLE MINIMUM.
 ** PLEASE BE SURE TO SEE NEC 700.12F FOR CIRCUITING OF
 THESE FIXTURES.
  
 10) NOTE: PLEASE SUBMIT THE LOAD CALCULATIONS WHICH
 INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
  
 ** PLEASE KNOW ONE SET OF PLANS MAY BE RETAINED BY THIS
 OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]