| | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 2)2004 FBC EXISTING |
| | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 3) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT IS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT |
| | . ------------------------------------- |
| | ) NUMBER OF UNITS |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF ROOMS |
| | ) SQ. FT. FOOTPRINT |
| | |
| | 4)ADDITIONAL INFORMATION REQUIRED, 106.1.2*. PLANS |
| | INDICATE THERE IS A MEZZANINE LEVEL, PROVIDE WHAT WALLS |
| | ARE FOR THE FIRST FLOOR AND MEZZANINE LEVEL. |
| | |
| | 5) FBC 505.4. A MEZZANINE SHALL BE OPEN AND |
| | UNOBSTRUCTED TO THE ROOM IN WHICH SUCH MEZZANINE IS |
| | LOCATED EXCEPT FOR WALL NOT MORE THAN 42 INCHES HIGH, |
| | COLUMNS AND POSTS. |
| | |
| | 6)SUBMIT ELEVATION DRAWINGS SHOWING THE CLEAR HEIGHT |
| | ABOVE AND BELOW THE MEZZANINE FLOOR WHICH SHALL NOT BE |
| | LESS THAN 7 FEET. THE AREA OF A MEZZANINE SHALL NOT |
| | EXCEED ONE-THIRD OF THE AREA OF THAT ROOM OR SPACE IN |
| | WHICH IT IS LOCATED. FBC.505.1 AND 505.2 |
| | |
| | 7)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION |
| | BASE ON INTERIOR FINISH REQUIREMENTS BASED ON |
| | OCCUPANCY |
| | |
| | 8)PROVIDE A LIFE SAFETY PLAN SHOWING THE EXIT ACCESS |
| | TRAVEL DISTANCE. FBC 1013 ? 1016. |
| | |
| | 9)A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS |
| | A RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |