Plan Review Notes
Plan Review Notes For Permit 07080716
Permit Number 07080716
Review Stop M
Sequence Number 1
Notes
Date Text
2007-10-04 17:38:55PLEASE PROVIDE THE LEVEL OF ALTERATION YOU ARE DOING
 1,2 OR 3
 PLEASE CHECK THE OUT SIDE AIR CALCULATIONS IN THE
 DINING AREA.
 PLESAE PROVIDE EXHAUST FAN DUCT SIZE FOR EF 17 PAGE
 M2.1.
 PLEASE PROVIDE A EXHAUST FAN AND EQUIPMENT SCHEDULE ON
 THE PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732