| Plan Review Notes For Permit 07080716 |
| Permit Number |
07080716 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-23 11:54:10 | *****DENIED***** | | | | | | | | | 1.THE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 2.ON SHEET CS-01 UNDER THE APPLICABLE NFPA CODES, | | | STANDARDS, AND GUIDELINES SECTION, AMEND TO REFLECT | | | NFPA 75 - 2003 EDITION AND NFPA 780 - 2004 EDITION ARE | | | BEING REFERENCED. | | | | | | 3.THE BUILDING OR PORTION OF THE BUILDING SHALL BE | | | PERMITTED TO BE OCCUPIED DURING THIS SCOPE OF WORK ONLY | | | WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE | | | PROTECTION FEATURES ARE IN PLACE AND MAINTAINED. | | | | | | 4.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW | | | WALL AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS | | | C. | | | | | | 5.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | FIRE SPRINKLER AND/OR THE FIRE ALARM SYSTEM REMODEL. | | | | | | 6.WHEN/IF IT IS NECESSARY TO SHUT DOWN THE FIRE | | | PROTECTION SYSTEM DUE TO AN ALTERATION OR MODIFICATION, | | | THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN THE SYSTEM | | | IS SHUT DOWN AND WHEN IT IS RETURNED TO SERVICE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|