Plan Review Notes
Plan Review Notes For Permit 07080716
Permit Number 07080716
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-23 11:54:10*****DENIED*****
  
  
 1.THE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.ON SHEET CS-01 UNDER THE APPLICABLE NFPA CODES,
 STANDARDS, AND GUIDELINES SECTION, AMEND TO REFLECT
 NFPA 75 - 2003 EDITION AND NFPA 780 - 2004 EDITION ARE
 BEING REFERENCED.
  
 3.THE BUILDING OR PORTION OF THE BUILDING SHALL BE
 PERMITTED TO BE OCCUPIED DURING THIS SCOPE OF WORK ONLY
 WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION FEATURES ARE IN PLACE AND MAINTAINED.
  
 4.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 WALL AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
 5.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER AND/OR THE FIRE ALARM SYSTEM REMODEL.
  
 6.WHEN/IF IT IS NECESSARY TO SHUT DOWN THE FIRE
 PROTECTION SYSTEM DUE TO AN ALTERATION OR MODIFICATION,
 THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN THE SYSTEM
 IS SHUT DOWN AND WHEN IT IS RETURNED TO SERVICE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722