Plan Review Notes
Plan Review Notes For Permit 07080716
Permit Number 07080716
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-16 12:48:012007-09-16 12:48:01
  
 ** DENIED **
  
 ** PLEASE KNOW THERE ARE ONLY MINOR COMMENTS AT THIS
 TIME.
  
 1) NOTE:PLEASE SEE PROJECT IS ONLY SUBMITTED FOR
 *PLAN REVIEW* AND HAS NOT BEEN SUBMITTED FOR PERMIT
 APPLICATION.
 REVIEW STATUS WILL REMAIN IN *FAILED* STATUS UNTIL
 PERMIT APPLICATION AHS BEEN MADE EVEN WHEN PLANS ARE
 CODE COMPLIANT AND OK WITH CODE REVIEW.
 LICENSING, ETC IS VERIFIED AT TIME OF APPLICATION ETC
 BEFORE ISSUANCE FOR CONTRACTORS, DESIGNERS ETC.
 PLEASE PROVIDE THE ADDRESS OF LOCATION OF PROJECT ON
 PLANS. PLEASE SEE THE ADDRESS OF THE APPLIED LOCATION
 IS 315 S FLAGLER DR.
 FAC 61G1-16.004, 61G15-23.002,
 FBC ADMIN SECT, 106.1.2, 106.3.5.1.2, 110.1.2 ETC
  
 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 SOME ARE SHOWN; HOWEVER THE 2002 NEC IS BEING
 INDICATED.
  
 2) NOTE: PLEASE CLARIFY RISER AS SHOWN. THE FEEDERS
 SHOWN ARE IN DARK LINES LIKE THEY ARE BEING REPLACED
 AND SOME ARE NOTED TO HAVE *EQUIPMENT GROUNDING
 CONDUCTORS8 BEING PULLED IN.
 PLEASE CLARIFY WHICH SCOPE OF WORK IS BEING PERFORMED.
 ARE ALL AS SHOWN WITH DARK LINES BEING RE-PULLED? ** AS
 A NOTE: PLEASE SEE HOUSE BILL 7121 PASSED 7/19/06 WHICH
 MAY AFFECT THIS BUILDING. THIS IS ONLY NOTED AND IS
 BEING HANDLED THROUGH THE STATE. THIS IS FOR
 INFORMATIONAL PURPOSE ONLY.
  
 3) NOTE: PLEASE SEE LIGHTING CONTROL DEVICES BEING
 REPLACED TO MEET 13-415.1.ABC.1.2, 13-101. PLEASE
 VERIFY THE TYPE OF LIGHTING CONTROLS BEING INSTALLED
 AND USE IN AREAS.
  
 4) NOTE: PLEASE PROVIDE THE MAXIMUM LIGHTING POWER
 DENSITIES FOR THE ROOMS/SPACES WITH NEW LIGHTING
 FIXTURES.
 13-415.2
  
 5) NOTE: THE MINIMUM CANDELA LEVELS WERE FOUND ON SHEET
 E3.2 FOR FBC CHAPTER 11 ADA, HOWEVER PLEASE CLARIFY
 LEVELS FOR HORNS.
 11-4.28,.1, .2 AND.3.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]