| 2007-09-20 16:10:42 | BUILDING PLAN REVIEW |
| | PERMIT: 07080716 |
| | ADD: 315 S FLAGLER DR |
| | CONT: ?PLAN REVIEW? |
| | TEL: (561)655-8544 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT |
| | STATEMENT --- |
| | PLEASE DO |
| | NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT APPLICATION AFTER JULY |
| | 1,2007 (BUILDING) WILL BE REVIEWED UNDER THE 2004 FBC |
| | WITH THE 2007 REVISIONS. PLEASE SEE CS-01 APPLICABLE |
| | CODES AND CORRECT. |
| | |
| | 4) SHEET CS-01 BUILDING OCCUPANCY CLASSIFICATION, |
| | PLEASE CORRECT THE BUILDING TYPE, |
| | THE PLANS DO NOT INDICATE WHAT TYPE OF OCCUPANCY IS |
| | ABOVE THE 4TH FLOOR, THE I-2 OCCUPANCY ONLY ALLOWS |
| | 4FLOORS WITH AN ADDITIONAL STORY FOR A FULLY SPRINKLED |
| | BUILDING. |
| | THE CLASSIFICATION OF A **IA** BUILDING WOULD PROVIDE |
| | UNLIMITED HEIGHT. PLEASE REVIEW BUILDING TYPE. THIS |
| | WILL EFFECT THE FLOOR CEILING PENETRATIONS BY ONE HOUR, |
| | SEE TABLE 601. |
| | |
| | 5)THE FLOOR CEILING ASSEMBLY MAY POSSIBLY HAVE NEW |
| | PENETRATIONS THROUGH THE RATED |
| | ASSEMBLY.PLEASE PROVIDE PRODUCT INFORMATION FOR THE |
| | FIRESTOP SYSTEM FOR THROUGH-PENETRATIONS. SEE 712.4.2. |
| | |
| | 6) SHEET A-02 INDICATES THE USE OF CROWN MOLDINGS AND |
| | CHAIR RAIL SYSTEM, PLEASE INDICATE THE TYPE OF |
| | MATERIALS FOR THE TRIM PACKAGE. SEE 805.3 & 2604.2. |
| | |
| | 7) COMBUSTIBLE DECORATIONS IN I-2 OCCUPANCIES. 805.1 |
| | GENERAL. |
| | IN OCCUPANCIES OF GROUPS A, E, I, R-1 AND DORMITORIES |
| | IN GROUP R-2, CURTAINS, DRAPERIES, HANGINGS AND OTHER |
| | DECORATIVE MATERIALS SUSPENDED FROM WALLS OR CEILINGS |
| | SHALL BE FLAME RESISTANT IN ACCORDANCE WITH SECTION |
| | 805.2 AND NFPA 701 OR NONCOMBUSTIBLE. |
| | IN GROUPS I-1 AND I-2 , COMBUSTIBLE DECORATIONS SHALL |
| | BE FLAME RETARDANT UNLESS THE DECORATIONS, SUCH AS |
| | PHOTOGRAPHS AND PAINTINGS, ARE OF SUCH LIMITED |
| | QUANTITIES THAT A HAZARD OF FIRE DEVELOPMENT OR SPREAD |
| | IS NOT PRESENT. IN GROUP I-3, COMBUSTIBLE DECORATIONS |
| | ARE PROHIBITED. |
| | |
| | 8) SHEET A-03 SOUND INSULATION, THE PLANS INDICATE A |
| | NOTE# 3, NOT FOUND ON THIS SHEET. |
| | PLEASE PROVIDE PRODUCT INFORMATION.719.2 CONCEALED |
| | INSTALLATION. |
| | INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| | BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |