Plan Review Notes
Plan Review Notes For Permit 07080716
Permit Number 07080716
Review Stop B
Sequence Number 1
Notes
Date Text
2007-09-20 16:10:42BUILDING PLAN REVIEW
 PERMIT: 07080716
 ADD: 315 S FLAGLER DR
 CONT: ?PLAN REVIEW?
 TEL: (561)655-8544
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT
 STATEMENT ---
 PLEASE DO
 NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT APPLICATION AFTER JULY
 1,2007 (BUILDING) WILL BE REVIEWED UNDER THE 2004 FBC
 WITH THE 2007 REVISIONS. PLEASE SEE CS-01 APPLICABLE
 CODES AND CORRECT.
  
 4) SHEET CS-01 BUILDING OCCUPANCY CLASSIFICATION,
 PLEASE CORRECT THE BUILDING TYPE,
 THE PLANS DO NOT INDICATE WHAT TYPE OF OCCUPANCY IS
 ABOVE THE 4TH FLOOR, THE I-2 OCCUPANCY ONLY ALLOWS
 4FLOORS WITH AN ADDITIONAL STORY FOR A FULLY SPRINKLED
 BUILDING.
 THE CLASSIFICATION OF A **IA** BUILDING WOULD PROVIDE
 UNLIMITED HEIGHT. PLEASE REVIEW BUILDING TYPE. THIS
 WILL EFFECT THE FLOOR CEILING PENETRATIONS BY ONE HOUR,
 SEE TABLE 601.
  
 5)THE FLOOR CEILING ASSEMBLY MAY POSSIBLY HAVE NEW
 PENETRATIONS THROUGH THE RATED
 ASSEMBLY.PLEASE PROVIDE PRODUCT INFORMATION FOR THE
 FIRESTOP SYSTEM FOR THROUGH-PENETRATIONS. SEE 712.4.2.
  
 6) SHEET A-02 INDICATES THE USE OF CROWN MOLDINGS AND
 CHAIR RAIL SYSTEM, PLEASE INDICATE THE TYPE OF
 MATERIALS FOR THE TRIM PACKAGE. SEE 805.3 & 2604.2.
  
 7) COMBUSTIBLE DECORATIONS IN I-2 OCCUPANCIES. 805.1
 GENERAL.
 IN OCCUPANCIES OF GROUPS A, E, I, R-1 AND DORMITORIES
 IN GROUP R-2, CURTAINS, DRAPERIES, HANGINGS AND OTHER
 DECORATIVE MATERIALS SUSPENDED FROM WALLS OR CEILINGS
 SHALL BE FLAME RESISTANT IN ACCORDANCE WITH SECTION
 805.2 AND NFPA 701 OR NONCOMBUSTIBLE.
 IN GROUPS I-1 AND I-2 , COMBUSTIBLE DECORATIONS SHALL
 BE FLAME RETARDANT UNLESS THE DECORATIONS, SUCH AS
 PHOTOGRAPHS AND PAINTINGS, ARE OF SUCH LIMITED
 QUANTITIES THAT A HAZARD OF FIRE DEVELOPMENT OR SPREAD
 IS NOT PRESENT. IN GROUP I-3, COMBUSTIBLE DECORATIONS
 ARE PROHIBITED.
  
 8) SHEET A-03 SOUND INSULATION, THE PLANS INDICATE A
 NOTE# 3, NOT FOUND ON THIS SHEET.
 PLEASE PROVIDE PRODUCT INFORMATION.719.2 CONCEALED
 INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]