Plan Review Notes
Plan Review Notes For Permit 07080712
Permit Number 07080712
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-04 10:29:32***APPROVED/PROVISO***
  
 1) FIRE DEPARTMENT CONNECTION SHALL NOT BE OBSTRUCTED.
 2) FIRE DEPARTMENT CONNECTION TO FACE TOWARD FIRE
 APPARATUS.
 3) KNOX LOCKING CAPS REQUIRED ON FDC.
 4) IN ADDITION TO ELECTRONIC SUPERVISION, CHAIN AND
 LOCK REQUIRED ON DOUBLE DETECTOR CHECK VALVES.
 5) STANDPIPE CONNECTIONS TO BE 2 1/2"-1 1/2" REDUCER
 WITH CHAINS.
 6) FIRE SPRINKLER COVERAGE REQUIRED AT TOP OF BOTH
 STAIRWELLS. NOT ILLUSTRATED IN SOUTH STAIRWELL.