| 2007-09-04 10:29:32 | ***APPROVED/PROVISO*** | | | | | | 1) FIRE DEPARTMENT CONNECTION SHALL NOT BE OBSTRUCTED. | | | 2) FIRE DEPARTMENT CONNECTION TO FACE TOWARD FIRE | | | APPARATUS. | | | 3) KNOX LOCKING CAPS REQUIRED ON FDC. | | | 4) IN ADDITION TO ELECTRONIC SUPERVISION, CHAIN AND | | | LOCK REQUIRED ON DOUBLE DETECTOR CHECK VALVES. | | | 5) STANDPIPE CONNECTIONS TO BE 2 1/2"-1 1/2" REDUCER | | | WITH CHAINS. | | | 6) FIRE SPRINKLER COVERAGE REQUIRED AT TOP OF BOTH | | | STAIRWELLS. NOT ILLUSTRATED IN SOUTH STAIRWELL. |
|