| Date |
Text |
| 2008-04-07 15:10:54 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW ARE STILL IN |
| | NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS DUE TO |
| | CHANGES MADE TO PLANS NOT IN ORIGINAL REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE THE TITLE BLOCKS HAVE BEEN REVISED |
| | TO SHOW A NEW DESIGNER OF RECORD. |
| | PLEASE ALSO SEE THE NEW DESIGN FIRM IS MISSING REQUIRED |
| | CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED PER FS |
| | 471.023 AND FAC 61G15-23.002. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE SEE MINIMUM LIGHTING CONTROLS FOR NEW |
| | BATHROOMS ARE NOT BEING SHOWN PER 13-415.1.ABC.1.1, |
| | .1.2. |
| | |
| | 3) NOTE: PLEASE SEE NO MAXIMUM LIGHTING LEVELS ARE |
| | SHOWN PER 13-415.2, 13-415.2.ABC.1.1 ETC. |
| | PLEASE SUBMIT AND SHOW. |
| | |
| | 4) NOTE: PLEASE SEE NO CIRCUITING IS SHOWN AND NOT |
| | CIRCUITING FOR EMERGENCY LIGHTS IS BEING SHOWN. A NOTE |
| | WAS ADDED TO PLANS HOWEVER NOTES IN LIEU OF MINIMUM |
| | DETAILS IS NOT PERMITTED. |
| | |
| | 5) NOTE: PLEASE COMPLETE PLANS WITH MINIMUMS REQUIRED |
| | PER CODES. |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |