| Plan Review Notes For Permit 07080709 |
| Permit Number |
07080709 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-17 23:24:23 | ***** DENIED****** | | | | | | | | | 1.STRUCTURES UNDERGOINGCONSTRUCTION, ALTERATIONS, | | | OR DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.SPECIFY THE WALL AND CEILING INTERIOR FINISH | | | MATERIALIN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 3.SEPARATE PLANS ANDPERMITREQUIRED FORFIRE | | | ALARM REMODEL. | | | | | | 4.NFPA 72- 2002 EDITION, NATIONAL FIRE ALARM CODE, | | | SHALL BE REFERENCED. | | | | | | 5.AMEND FIRE ALARM NOTE IN REFERENCE TO HVAC DUCT | | | SMOKE DETECTORS TO REFLECT THAT THEY SHALL INITIATE A | | | GENERAL FIRE ALARM. | | | | | | 6.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EGRESS FROM OR ACCESS TO OTHER SPACES ON THE FLOOR OR | | | THE BUILDING. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHEREON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|