Plan Review Notes
Plan Review Notes For Permit 07080709
Permit Number 07080709
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-08 19:33:002007-09-08 19:33:00
  
 ** DENIED **
  
  
  
 1) NOTE:PLEASE SEE SHEET 3, NOTES FOR FIRE ALARM
 WHICH MENTIONS NPPA. THIS SHOULD BE NFPA. PLEASE
 ADJUST.(MISPRINT)
  
 2) NOTE: PLEASE SEE THAT HAND WRITTEN ITEMS ON SIGNED,
 DATED AND SEALED PLANS ARE NOT PERMITTED.
 PLEASE RE-PRINT.
 FS 471.025
  
 3) NOTE: PLEASE SEE NOTES FOR FIRE ALARM MENTIONS
 SECURITY LOCKING SYSTEM HOWEVER PLANS DO NOT SHOW ANY
 OF THESE ITEMS OR FAIL SAFE OPERATION SO THAT EGRESS IN
 NOT IMPEDED UNDER EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101 CHAPTER 7. 7.2.1.5, 7.2.1.6.2
  
 4) NOTE: PLEASE INDICATE THE CIRCUITING FOR THE
 EMERGENCY BATTERY BACK UP LIGHT FIXTURE PER 700.12F. **
 SHALL BE CIRCUITED TO THE NORMAL BRANCH CIRCUIT WHICH
 FEEDS THE OTHER LIGHTING IN THE AREA BEING SERVED.
  
 5) NOTE: PLEASE SEE A NOTE ON SHEET 3 MENTIONS THIS IS
 A DWELLING??
 PLEASE ADJUST. PLEASE ALSO SEE BUILDING REVIEW COMMENTS
 FOR LEVEL OF ALTERATION.
  
 6) NOTE: PLEASE SEE THE REQUIREMENTS FOR LIGHTING
 CONTROLS FOR NEW DEVICES PER13-415.1.ABC.1.1, .1.2.
 PLEASE SEE THE TYPE OF DEVICE SHALL NOT ONLY BE MOTION
 SENSOR AS THERE ARE STALL WALLS WHICH WOULD AFFECT
 PERFORMANCE OF DEVICE.
 PLEASE SEE 13-415.2 FOR SPECIFIC LIGHTING LEVEL TO BE
 INDICATED. (MAX FOR BATHROOMS).
 13-101.
  
 7) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR STROBES
 AND OR HORN DEVICES TO MEET FBCFOR ADA. PLEASE SEE
 11-4.28.1, .2, AND .3(4).
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved