| Date |
Text |
| 2007-09-08 19:33:00 | 2007-09-08 19:33:00 |
| | |
| | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE:PLEASE SEE SHEET 3, NOTES FOR FIRE ALARM |
| | WHICH MENTIONS NPPA. THIS SHOULD BE NFPA. PLEASE |
| | ADJUST.(MISPRINT) |
| | |
| | 2) NOTE: PLEASE SEE THAT HAND WRITTEN ITEMS ON SIGNED, |
| | DATED AND SEALED PLANS ARE NOT PERMITTED. |
| | PLEASE RE-PRINT. |
| | FS 471.025 |
| | |
| | 3) NOTE: PLEASE SEE NOTES FOR FIRE ALARM MENTIONS |
| | SECURITY LOCKING SYSTEM HOWEVER PLANS DO NOT SHOW ANY |
| | OF THESE ITEMS OR FAIL SAFE OPERATION SO THAT EGRESS IN |
| | NOT IMPEDED UNDER EMERGENCY CONDITIONS. |
| | PLEASE SEE NFPA-101 CHAPTER 7. 7.2.1.5, 7.2.1.6.2 |
| | |
| | 4) NOTE: PLEASE INDICATE THE CIRCUITING FOR THE |
| | EMERGENCY BATTERY BACK UP LIGHT FIXTURE PER 700.12F. ** |
| | SHALL BE CIRCUITED TO THE NORMAL BRANCH CIRCUIT WHICH |
| | FEEDS THE OTHER LIGHTING IN THE AREA BEING SERVED. |
| | |
| | 5) NOTE: PLEASE SEE A NOTE ON SHEET 3 MENTIONS THIS IS |
| | A DWELLING?? |
| | PLEASE ADJUST. PLEASE ALSO SEE BUILDING REVIEW COMMENTS |
| | FOR LEVEL OF ALTERATION. |
| | |
| | 6) NOTE: PLEASE SEE THE REQUIREMENTS FOR LIGHTING |
| | CONTROLS FOR NEW DEVICES PER13-415.1.ABC.1.1, .1.2. |
| | PLEASE SEE THE TYPE OF DEVICE SHALL NOT ONLY BE MOTION |
| | SENSOR AS THERE ARE STALL WALLS WHICH WOULD AFFECT |
| | PERFORMANCE OF DEVICE. |
| | PLEASE SEE 13-415.2 FOR SPECIFIC LIGHTING LEVEL TO BE |
| | INDICATED. (MAX FOR BATHROOMS). |
| | 13-101. |
| | |
| | 7) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR STROBES |
| | AND OR HORN DEVICES TO MEET FBCFOR ADA. PLEASE SEE |
| | 11-4.28.1, .2, AND .3(4). |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |