Plan Review Notes
Plan Review Notes For Permit 07080695
Permit Number 07080695
Review Stop P
Sequence Number 3
Notes
Date Text
2007-12-21 11:19:32****************PROVISO****************
 A} PER TABLE *604 MINIMUM SIZE OF FIXTURE WATER SUPPLY
 PIPES THE NEW HAND SINK WATER PIPES SHALL BE MINIMUM
 SIZE 1/2".
  
 B}802.1.1 FOOD HANDLING.
 EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
  
  
 C} PER TABLE 909.3 WET VENT SIZE: THE EXISTING
 BATHROOM VENT NEEDS TO BE INCREASED TO 3", OR SUPPLY AN
 AIR ADMITTANCE VALVE FOR NEW HAND SINK COMPLIANT WITH
 SECTION *917. (REVISION REQUIRED BEFORE FINAL)
  
 D} EXISTING MOP SINK SHALL DISCHARGE INTO THE GREASE
 SYSTEM PER SECTION *1003, INTERCEPTORS AND SEPERATORS.
 (REVISION REQUIRED BEFORE FINAL)
  
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED FOR NEW APPLIANCES IN
 KITCHEN. LICENSED GAS OR PLUMBING CONTRACTOR TO SUBMIT
 PLANS WITH PERMIT APPLICATION. ALL GAS INSPECTIONS TO
 BE COMPLETE BEFORE FINAL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
 ******PROVISO******
 PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A DEMO PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  