| 2007-12-21 11:19:32 | ****************PROVISO**************** |
| | A} PER TABLE *604 MINIMUM SIZE OF FIXTURE WATER SUPPLY |
| | PIPES THE NEW HAND SINK WATER PIPES SHALL BE MINIMUM |
| | SIZE 1/2". |
| | |
| | B}802.1.1 FOOD HANDLING. |
| | EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE, |
| | PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE |
| | THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. |
| | |
| | |
| | C} PER TABLE 909.3 WET VENT SIZE: THE EXISTING |
| | BATHROOM VENT NEEDS TO BE INCREASED TO 3", OR SUPPLY AN |
| | AIR ADMITTANCE VALVE FOR NEW HAND SINK COMPLIANT WITH |
| | SECTION *917. (REVISION REQUIRED BEFORE FINAL) |
| | |
| | D} EXISTING MOP SINK SHALL DISCHARGE INTO THE GREASE |
| | SYSTEM PER SECTION *1003, INTERCEPTORS AND SEPERATORS. |
| | (REVISION REQUIRED BEFORE FINAL) |
| | |
| | CONTRACTOR INFORMATION |
| | NOTE: GAS PERMIT REQUIRED FOR NEW APPLIANCES IN |
| | KITCHEN. LICENSED GAS OR PLUMBING CONTRACTOR TO SUBMIT |
| | PLANS WITH PERMIT APPLICATION. ALL GAS INSPECTIONS TO |
| | BE COMPLETE BEFORE FINAL INSPECTION. |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |
| | |
| | ******PROVISO****** |
| | PER FBC-2004 PLUMBING, SECTION 704.5 |
| | DEAD ENDS: IN THE INSTALLATION OR |
| | REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| | A DEMO PLUMBING PERMIT REQUIRED AND |
| | INSPECTION REQUIRED OF DEMO WORK PRIOR |
| | TO COVERING DEMO WORK WITH FINNISH |
| | WALLS, CIELINGS, OR POURED CONCRETE |
| | SLABS. |
| | |