| Date |
Text |
| 2007-12-10 10:27:55 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS |
| | TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | **PLEASE KNOW THERE ARE STILL SOME COMMENTS FROM |
| | PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG |
| | WITH NEW COMMENTS DUE TO ITEMS NOW REVISED ON PLANS |
| | WHICH WERE NOT ON ORIGINAL PLANS. |
| | |
| | 1. OK, COMMENT ADDRESSED. |
| | |
| | 2. SITE PLAN INDICATES AN EXISTING GREASE TRAP WITH NO |
| | SIZE BEING INDICATED, PLEASE NOTE THAT THE EXISTING |
| | GREASE TRAP WILL NEED TO BE APPROVED PER THE FOLLOWING. |
| | PER MUNICIPAL CODE ARTICLE III SECTION 90-124, |
| | THE EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED |
| | AND LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE |
| | UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: |
| | (561) 822-2272, E-MAIL: [email protected] OR CLAVIN |
| | WILLIAMS, PHONE: (561) 822-2284, E-MAIL: |
| | [email protected]. THEIR FAX NUMBER IS (561) 822-2287. |
| | NOTE: WRITTEN APPROVAL IS REQUIRED OF THE |
| | EXISTING/PROPOSED GREASE INTERCEPTOR FROM ENVIRONMENTAL |
| | COMPLIANCE BEFORE A PERMIT CAN BE ISSUED. |
| | **RESPONSE NOTED: THIS COMMENT WAS ADDRESSED HOWEVER |
| | THE RESUBMITTED PLANS SHEET, SITE PLAN ARE INDICATING |
| | THE EXISTING 750 GAL GREASE INTERCEPTOR IN THE NEW |
| | OUTSIDE DECK AREA, PLEASE CLARIFY HOW ACCESS TO THE |
| | EXISTING 750 GAL. GREASE INTERCEPTOR FOR ROUTINE |
| | MAINTENANCE WILL BE ACHEIVED IF ITS COVERED BY A NEW |
| | OUTSIDE DECK. PER *801.1 SCOPE. |
| | |
| | **NOTE SHEET, RISER PLAN: THIS SHEET IS INDICATING A |
| | NEW ZURN GREASE INTERCEPTOR 2700-25 FLOW RATE = 25 |
| | CAPACITY 50LB FOR THE RELOCATED 3 COMP. SINK BEING TIED |
| | INTO THE EXISTING SANITARY SYSTEM. THIS WAS NOT |
| | APPROVED BY ENVIRONMENTAL COMPLIANCE ON THE ATTACHED |
| | CALCULATION FOR RESTAURANT INTERCEPTOR SHEET. ARROVAL |
| | OF THIS ADDED GREASE TRAP FOR THE 3 COMP. SINK IS |
| | REQUIRED FROM ENVIRONMENTAL COMPLIANCE AND SHALL BE |
| | NOTED ON THE CALCULATION FOR RESTAURANT INTERCEPTOR |
| | PRIOR TO PERMIT APPROVAL OR THE RELOCATED 3 COMP. SINK |
| | WASTE WILL NEED TO DRAIN INTO THE EXISTING 4" GREASE |
| | LINE. PER 1103 INTERCEPTORS AND SEPERATORS. |
| | |
| | 3. OK, COMMENT ADDRESSED. |
| | |
| | 4. OK, COMMENT ADDRESSED. |
| | **NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING |
| | CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION WITH |
| | THE FOLLOWING INFORMATION. ALL GAS INSPECTIONS TO BE |
| | COMPLETE BEFORE FINAL INSPECTION. |
| | |
| | **CONTRACTOR INFORMATION** |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | J. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 6.6.1. |
| | |
| | L. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | 5. OK, COMMENT ADDRESSED. |
| | |
| | 6. OK, COMMENT ADDRESSED. |
| | |
| | 7. PLEASE PROVIDE A SANITARY, GREASE AND WATER |
| | ISOMETRIC RISER DIAGRAM OF ALL NEW PROPOSED FIXTURES |
| | PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3. |
| | **RESPONSE NOTED: HOWEVER NEW COMMENTS PER EACH SYSTEM |
| | TO FOLLOW. |
| | |
| | 8. OK, COMMENT ADDRESSED. |
| | |
| | **THE FOLLOWING ARE NEW COMMENTS** |
| | |
| | 9. SHEET, RISER PLAN, SANITARY RISER: PLEASE DELETE |
| | THE DEMO WORK FROM THE PROPOSED SANITARY RISER DIAGRAM. |
| | (CAP EXISTING LAV, CAP EXISTING W/C, CAP RELOCATED 3 |
| | COMP.). PER *701.1 SCOPE. |
| | |
| | 10. SHEET, RISER PLAN, SANITARY RISER: CLEARLY |
| | IDENTIFY ALL PLUMBING FIXTURES FOR THE INDICATED TRAPS. |
| | WHERE'S THE NEW HAND SINK? PER *701.1 SCOPE. |
| | |
| | 11. SHEET, RISER PLAN, GREASE RISER: CLEARLY SIZE |
| | IDENTIFY WHAT EACH F.S. IS DRAINING ON THE GREASE |
| | SYSTEM. PER *1001.1 SCOPE. |
| | |
| | 12. SHEET, RISER PLAN, GREASE RISER: TRAPS ARE |
| | REQUIRED FOR THE F.S. PER *1002.1 FIXTURE TRAPS. |
| | |
| | 13. SHEET, RISER PLAN, GREASE RISER: A VENT IS |
| | REQUIRED FOR THE COMBINATION WASTE AND VENT SYSTEM. |
| | PLEASE INDICATE THE REQUIRED VENT ON THE RESUBMITTAL. |
| | PER *912.2.2 CONNECTION, AND VENT SHALL BE SIZED PER |
| | TABLE *912.3. |
| | |
| | 14. SHEET, RISER PLAN, POTABLE WATER: ALL NEW AS WELL |
| | AS THE RELOCATED PLUMBING FIXTURES NEED TO BE ON THE |
| | POTABLE WATER RISER DIAGRAM. WHERE'S THE NEW HAND SINK? |
| | PER *601.1 SCOPE. |
| | |
| | 15. SHEET, RISER PLAN, POTABLE WATER: AIR CHAMBERS ARE |
| | NOT ALLOWED. PLEASE DELETE THESE ON THE RESUBMITTAL. |
| | PER *604.9 WATER HAMMER. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |