Plan Review Notes
Plan Review Notes For Permit 07080695
Permit Number 07080695
Review Stop P
Sequence Number 2
Notes
Date Text
2007-12-10 10:27:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 **PLEASE KNOW THERE ARE STILL SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG
 WITH NEW COMMENTS DUE TO ITEMS NOW REVISED ON PLANS
 WHICH WERE NOT ON ORIGINAL PLANS.
  
 1. OK, COMMENT ADDRESSED.
  
 2. SITE PLAN INDICATES AN EXISTING GREASE TRAP WITH NO
 SIZE BEING INDICATED, PLEASE NOTE THAT THE EXISTING
 GREASE TRAP WILL NEED TO BE APPROVED PER THE FOLLOWING.
 PER MUNICIPAL CODE ARTICLE III SECTION 90-124,
 THE EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED
 AND LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE
 UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE:
 (561) 822-2272, E-MAIL: [email protected] OR CLAVIN
 WILLIAMS, PHONE: (561) 822-2284, E-MAIL:
 [email protected]. THEIR FAX NUMBER IS (561) 822-2287.
 NOTE: WRITTEN APPROVAL IS REQUIRED OF THE
 EXISTING/PROPOSED GREASE INTERCEPTOR FROM ENVIRONMENTAL
 COMPLIANCE BEFORE A PERMIT CAN BE ISSUED.
 **RESPONSE NOTED: THIS COMMENT WAS ADDRESSED HOWEVER
 THE RESUBMITTED PLANS SHEET, SITE PLAN ARE INDICATING
 THE EXISTING 750 GAL GREASE INTERCEPTOR IN THE NEW
 OUTSIDE DECK AREA, PLEASE CLARIFY HOW ACCESS TO THE
 EXISTING 750 GAL. GREASE INTERCEPTOR FOR ROUTINE
 MAINTENANCE WILL BE ACHEIVED IF ITS COVERED BY A NEW
 OUTSIDE DECK. PER *801.1 SCOPE.
  
 **NOTE SHEET, RISER PLAN: THIS SHEET IS INDICATING A
 NEW ZURN GREASE INTERCEPTOR 2700-25 FLOW RATE = 25
 CAPACITY 50LB FOR THE RELOCATED 3 COMP. SINK BEING TIED
 INTO THE EXISTING SANITARY SYSTEM. THIS WAS NOT
 APPROVED BY ENVIRONMENTAL COMPLIANCE ON THE ATTACHED
 CALCULATION FOR RESTAURANT INTERCEPTOR SHEET. ARROVAL
 OF THIS ADDED GREASE TRAP FOR THE 3 COMP. SINK IS
 REQUIRED FROM ENVIRONMENTAL COMPLIANCE AND SHALL BE
 NOTED ON THE CALCULATION FOR RESTAURANT INTERCEPTOR
 PRIOR TO PERMIT APPROVAL OR THE RELOCATED 3 COMP. SINK
 WASTE WILL NEED TO DRAIN INTO THE EXISTING 4" GREASE
 LINE. PER 1103 INTERCEPTORS AND SEPERATORS.
  
 3. OK, COMMENT ADDRESSED.
  
 4. OK, COMMENT ADDRESSED.
 **NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION WITH
 THE FOLLOWING INFORMATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL INSPECTION.
  
 **CONTRACTOR INFORMATION**
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL)
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 6.6.1.
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 5. OK, COMMENT ADDRESSED.
  
 6. OK, COMMENT ADDRESSED.
  
 7. PLEASE PROVIDE A SANITARY, GREASE AND WATER
 ISOMETRIC RISER DIAGRAM OF ALL NEW PROPOSED FIXTURES
 PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3.
 **RESPONSE NOTED: HOWEVER NEW COMMENTS PER EACH SYSTEM
 TO FOLLOW.
  
 8. OK, COMMENT ADDRESSED.
  
 **THE FOLLOWING ARE NEW COMMENTS**
  
 9. SHEET, RISER PLAN, SANITARY RISER: PLEASE DELETE
 THE DEMO WORK FROM THE PROPOSED SANITARY RISER DIAGRAM.
 (CAP EXISTING LAV, CAP EXISTING W/C, CAP RELOCATED 3
 COMP.). PER *701.1 SCOPE.
  
 10. SHEET, RISER PLAN, SANITARY RISER: CLEARLY
 IDENTIFY ALL PLUMBING FIXTURES FOR THE INDICATED TRAPS.
 WHERE'S THE NEW HAND SINK? PER *701.1 SCOPE.
  
 11. SHEET, RISER PLAN, GREASE RISER: CLEARLY SIZE
 IDENTIFY WHAT EACH F.S. IS DRAINING ON THE GREASE
 SYSTEM. PER *1001.1 SCOPE.
  
 12. SHEET, RISER PLAN, GREASE RISER: TRAPS ARE
 REQUIRED FOR THE F.S. PER *1002.1 FIXTURE TRAPS.
  
 13. SHEET, RISER PLAN, GREASE RISER: A VENT IS
 REQUIRED FOR THE COMBINATION WASTE AND VENT SYSTEM.
 PLEASE INDICATE THE REQUIRED VENT ON THE RESUBMITTAL.
 PER *912.2.2 CONNECTION, AND VENT SHALL BE SIZED PER
 TABLE *912.3.
  
 14. SHEET, RISER PLAN, POTABLE WATER: ALL NEW AS WELL
 AS THE RELOCATED PLUMBING FIXTURES NEED TO BE ON THE
 POTABLE WATER RISER DIAGRAM. WHERE'S THE NEW HAND SINK?
 PER *601.1 SCOPE.
  
 15. SHEET, RISER PLAN, POTABLE WATER: AIR CHAMBERS ARE
 NOT ALLOWED. PLEASE DELETE THESE ON THE RESUBMITTAL.
 PER *604.9 WATER HAMMER.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved