Plan Review Notes
Plan Review Notes For Permit 07080695
Permit Number 07080695
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-27 16:39:59** DENIED2ND REVIEW **
  
 ** PLEASE KNOW THERE ARE STILL SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG
 WITH NEW COMMENTS DUE TO ITEMS NOW REVISED ON PLANS
 WHICH WERE NOT ON ORIGINAL PLANS.
  
 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES SHALL BE
 STATED ON PLANS AS THERE IS NEW WORK NOT IN ORIGINAL
 SCOPE.
 NFPA-70 2005
 NFPA-101 2003
  
 2) NOTE: PLEASE SEE THE RISER HAS NOW BEEN REVISED TO
 INCLUDE A NEW MAIN DISCONNECT HOWEVER NO AIC RATING WAS
 GIVEN.
 PLEASE INCLUDE PER 110.9
  
 3) NOTE: PLEASE SEE THE RISER STILL INDICATES PANELS AS
 CONTAINING A *MAIN* AND NOW INCLUDES A CLOUD AROUND THE
 WORDING *200AMP MAIN*, YET ONCE AGAIN BOTH PANELS ARE
 STILL SHOWN AS *MAIN LUG ONLY* ON THE PANEL SCHEDULES.
 PLEASE SHOW WHICH EXISTS OR WHICH IS NEW.
 ARE THESE MAIN LUG ONLY PANELS OR ARE THEY MAIN CIRCUIT
 BREAKER PANELS?
 230.70, 230.71 ETC
 FBC 106.3.5.1.2
  
 4) NOTE: PLEASE SEE THE PLANS STILL INDICATE THERE IS
 GOING TO BE NEW LIGHTING DUE TO THE NEW CIRCUITS BEING
 ADDED TO TIME CLOCKS, HOWEVER AS REQUESTED ON PREVIOUS
 PLANS, WHERE IS THIS NEW LIGHTING AND CIRCUITING SHOWN
 FOR NEW LIGHTS ON PLANS. (LAYOUT)
 PLEASE SEE THAT THE CIRCUITING FOR THE EM LIGHT FIXTURE
 IS TO BE CIRCUITED PER 700.12F.
  
 5) NOTE: PLEASE SEE NOW THAT A NEW MAIN DISCONNECT HAS
 BEEN ADDED IN FRONT THE PANELS, RISER IS NOW MISSING
 *EQUIPMENT GROUNDING CONDUCTORS* AFTER THE FIRST MEANS
 OF DISCONNECT.
 PLEASE SEE 250.24, 250.110, AND 250.122.
  
  
 6) NOTE: PLEASE SEE THE RISER SHOWS A NEW GROUNDING
 ELECTRODE SYSTEM HOWEVER DOES NOT INCLUDE ALL ITEMS ARE
 REQUIRED PER 250.50. ( METAL COLD WATER PIPE)
 PLEASE ALSO SHOW ANY GAS PIPING BONDING PER 250.104
  
 7) NOTE: PLEASE SHOW AND IDENTIFY ALL SERVICE PANELS ON
 PLANS. THIS WAS NOT ON PREVIOUS COMMENTS HOWEVER DUE TO
 SOME QUESTIONS ON DESIGN AND SAFETY PLEASE SHOW.
 FOR EXAMPLE, PLANS SHOW WHAT IS A SYMBOL FOR TWO PANELS
 HOWEVER ONE SEEMS TO BE SHOWN WHERE THE RAMP IS GOING
 TO BE INSTALLED WHICH WILL NOT MEET 110.26.
 PLEASE KNOW THAT PERMANENT BUILDING CONSTRUCTION IS NOT
 TO BE PLACED IN MINIMUM CLEARANCE AREAS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  