| 2007-11-27 16:39:59 | ** DENIED2ND REVIEW ** |
| | |
| | ** PLEASE KNOW THERE ARE STILL SOME COMMENTS FROM |
| | PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG |
| | WITH NEW COMMENTS DUE TO ITEMS NOW REVISED ON PLANS |
| | WHICH WERE NOT ON ORIGINAL PLANS. |
| | |
| | 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES SHALL BE |
| | STATED ON PLANS AS THERE IS NEW WORK NOT IN ORIGINAL |
| | SCOPE. |
| | NFPA-70 2005 |
| | NFPA-101 2003 |
| | |
| | 2) NOTE: PLEASE SEE THE RISER HAS NOW BEEN REVISED TO |
| | INCLUDE A NEW MAIN DISCONNECT HOWEVER NO AIC RATING WAS |
| | GIVEN. |
| | PLEASE INCLUDE PER 110.9 |
| | |
| | 3) NOTE: PLEASE SEE THE RISER STILL INDICATES PANELS AS |
| | CONTAINING A *MAIN* AND NOW INCLUDES A CLOUD AROUND THE |
| | WORDING *200AMP MAIN*, YET ONCE AGAIN BOTH PANELS ARE |
| | STILL SHOWN AS *MAIN LUG ONLY* ON THE PANEL SCHEDULES. |
| | PLEASE SHOW WHICH EXISTS OR WHICH IS NEW. |
| | ARE THESE MAIN LUG ONLY PANELS OR ARE THEY MAIN CIRCUIT |
| | BREAKER PANELS? |
| | 230.70, 230.71 ETC |
| | FBC 106.3.5.1.2 |
| | |
| | 4) NOTE: PLEASE SEE THE PLANS STILL INDICATE THERE IS |
| | GOING TO BE NEW LIGHTING DUE TO THE NEW CIRCUITS BEING |
| | ADDED TO TIME CLOCKS, HOWEVER AS REQUESTED ON PREVIOUS |
| | PLANS, WHERE IS THIS NEW LIGHTING AND CIRCUITING SHOWN |
| | FOR NEW LIGHTS ON PLANS. (LAYOUT) |
| | PLEASE SEE THAT THE CIRCUITING FOR THE EM LIGHT FIXTURE |
| | IS TO BE CIRCUITED PER 700.12F. |
| | |
| | 5) NOTE: PLEASE SEE NOW THAT A NEW MAIN DISCONNECT HAS |
| | BEEN ADDED IN FRONT THE PANELS, RISER IS NOW MISSING |
| | *EQUIPMENT GROUNDING CONDUCTORS* AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | PLEASE SEE 250.24, 250.110, AND 250.122. |
| | |
| | |
| | 6) NOTE: PLEASE SEE THE RISER SHOWS A NEW GROUNDING |
| | ELECTRODE SYSTEM HOWEVER DOES NOT INCLUDE ALL ITEMS ARE |
| | REQUIRED PER 250.50. ( METAL COLD WATER PIPE) |
| | PLEASE ALSO SHOW ANY GAS PIPING BONDING PER 250.104 |
| | |
| | 7) NOTE: PLEASE SHOW AND IDENTIFY ALL SERVICE PANELS ON |
| | PLANS. THIS WAS NOT ON PREVIOUS COMMENTS HOWEVER DUE TO |
| | SOME QUESTIONS ON DESIGN AND SAFETY PLEASE SHOW. |
| | FOR EXAMPLE, PLANS SHOW WHAT IS A SYMBOL FOR TWO PANELS |
| | HOWEVER ONE SEEMS TO BE SHOWN WHERE THE RAMP IS GOING |
| | TO BE INSTALLED WHICH WILL NOT MEET 110.26. |
| | PLEASE KNOW THAT PERMANENT BUILDING CONSTRUCTION IS NOT |
| | TO BE PLACED IN MINIMUM CLEARANCE AREAS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |