Plan Review Notes
Plan Review Notes For Permit 07080695
Permit Number 07080695
Review Stop B
Sequence Number 2
Notes
Date Text
2007-11-19 10:51:56GREAT WRAPS RESTARAUNT
 2409 S DIXIE HWY
 BUILDING PLAN REVIEW
 PERMIT: 07080695
 ADD: 2409 S DIXIE HWY
 CONT: L DAVIS CONSTRUCTION
 TEL: (561)718-8161
 NOV. 19,-2007
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)COMPLIED
  
 4) SINCE ADDITIONAL INFORMATION ON THE RAMP HAS BEEN
 PROVIDED ADDITIONAL INFORMATION IS REQUIRED OR CHANGES
 ARE REQUIRED DUE TO THE NEW INFORMATION.
 THE SHEET A-1 NOW INDICATES A RAMP WITH SLOPE OF 1 INCH
 IN 12 INCHES. THE PLAN INDICATES A RISE OF 8 INCHES BUT
 THE PLAN ONLY INDICATES A RUN OF 5FEET NOT THE EIGHT
 FEET REQUIRED FOR A RISE OF 8 INCHES.
 THE SECOND ISSUE WITH A RAMP THAT HAS A RISE OF 6
 INCHES OR MORE , WILL REQUIRE HANDRAILS ON BOTH SIDES .
 1.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN
 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT SHALL HAVE
 HANDRAILS ON BOTH SIDES.
 THE THIRD ISSUE IS THE CLOSENESS OF THE DOOR TO THE TOP
 OF THE RAMP. THE OUT-SWING DOOR NEXT TO THE RAMP WILL
 REQUIRE 18? CLEARANCE FROM THE EDGE OF THE DOOR TO THE
 BEGINNING OF THE RAMP. 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH IN
 THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 5)SECOND REQUEST, PLEASE PROVIDE CUT SECTION OF THE NEW
 OUTSIDE DECK, PLEASE INDICATE GRADE, ELEVATION ABOVE
 GRADE, SPAN, FRAMING MATERIALS, SIZE, SPECIES OF WOOD,
 FREQUENCY OF FRAMING MEMBERS, AND DECKING MATERIALS.
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
 SEE TABLE 1607.1 (6) OR (11) MINIMUM LIVE LOADS OF 100
 PSF.
  
 6-9) COMPLIED..
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  