Plan Review Notes
Plan Review Notes For Permit 07080695
Permit Number 07080695
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-22 16:56:57DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: TWO COMPLETE SETS OF THE DBPR WORK SHEETS ARE
 REQUIREDPER 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 2. SITE PLAN INDICATES AN EXISTING GREASE TRAP WITH NO
 SIZE BEING INDICATED. PLEASE NOTE THAT THE EXISTING
 GREASE TRAP WILL NEED TO BE APPROVED PER THE FOLLOWING.
 PER MUNICIPAL CODE ARTICLE III SECTION 90-124,
 THE EXISTING GREASE INTERCEPTOR SHALL BE SIZED AND
 LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE
 UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE:
 (561) 822-2272, E-MAIL: [email protected] OR CLAVIN
 WILLIAMS, PHONE: (561) 822-2284, E-MAIL:
 [email protected]. THEIR FAX NUMBER IS (561) 822-2287.
 NOTE: WRITTEN APPROVAL IS REQUIRED OF THE EXISTING
 GREASE INTERCEPTOR FROM ENVIRONMENTAL COMPLIANCE BEFORE
 A PERMIT CAN BE ISSUED.
  
 3. THE FOLLOWING HAND WRITTEN CHANGES TO THE PLANS ON
 SHEET A-1 H/S AND EXISTING MOP ARE UNACCEPTABLE PER
 CHAPTER 481, FLORIDA STATUTES, PART 1.
  
 4. SHEET A-1 FLOOR PLAN NOTES, (4) KITCHEN IS EXISTING
 (ADDING EQUIPMENT UNDER EXISTING HOOD)
 NOTE: CLEARLY IDENTIFY WHAT EQUIPMENT IS BEING ADDED
 UNDER THE HOOD AND IF THE EQUIPMENT IS GAS OR ELECTRIC,
 PER 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 5. SHEET A-1FLOOR PLAN: IS THE NEW GRIDDLE GAS OR
 ELECTRIC? PLEASE CLEARLY IDENTIFY ALL APPLIANCES AND
 FIXTURES IN THE PROPOSED RESTAURANT WITH A LEGEND
 CLEARLY INDICATING IF THEY ARE GAS, ELECTRIC, NEED
 HOT/COLD WATER WITH PIPE SIZES, TYPE OF DRAINAGE
 REQUIRED GREASE/SANITARY,PER 106.1.2 ADDITIONAL
 INFORMATION REQUIRED
  
 6. PER CHAPTER 1, SECTION 105THEPERMIT APPLICATION
 STATES "DESCRIBE PROJECT IN DETAIL (FAILURE TO DO SO
 MAY RESULT IN DELAYS)
 NOTE: THE FOLLOWING ARE NOT LISTED ON THE PERMIT
 APPLICATION:
  
 A} DEMO 1 EXISTING BATHROOM.
  
 B} DEMO 1 EXISTING 2 COMPARTMENT SINK.
  
 C} DEMO 1 RANGE/OVEN (UNDER EXISTING HOOD)
  
 D} DEMO PLANTERS.
  
 E} ADDING NEW GRIDDLE.
  
 F} ADDING 2 NEW FRYERS.
  
 G} ADDING 2 NEW HAND SINKS.
  
 H} ADDING 1 NEW 3 COMPARTMENT SINK (PER DBPR WORK
 SHEETS, NEEDS TO BE CLEARLY IDENTIFIED ON SHEET A-1).
  
 I} ADDING 1 NEW PASS THRU.
  
 J} ADDING NEW WALL AND DOOR BY SODA AND ICE MACHINE.
  
 NOTE: THE VALUE ON THE PERMIT SEEMS LOW WITH ALL THE
 WORK, NEW APPLIANCES AND FIXTURES BEING ADDED. PLEASE
 PROVIDE PROOF THAT THE ABOVE ITEMS ARE INCLUDED IN THE
 PERMIT VALUE WITH A COPY OF THE SIGNED CONTRACT. PLEASE
 PROVIDE PROOF OF FBC-2004 W/ 06 REV. SECTION
 11-4.(2)(A)BEING THAT THE EXISTING BATHROOMS ARE NOT
 ACCESSIBLE PER FBC-2004 W/06 REV. CHAPTER 11. PER
 FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 7. PLEASE PROVIDE A SANITARY/GREASE AND WATER
 ISOMETRIC RISER DIAGRAM OF ALL NEW PROPOSED FIXTURES
 PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3.
  
 A} THREE COMPARTMENT SINK.
 B} TWO HAND SINKS.
 NOTE: THE HAND SINK BY THE EXISTING WALK-IN COOLER IS
 MISLABELED AS EXISTING. THE DEMO PLANS DO NOT INDICATE
 THIS SINK BY THE COOLERS. HOW CAN THIS BE EXISTING?
  
 8. DEMO PLANS INDICATE A BATHROOM AND EXISITING 2
 COMPARMENT SINK FOR DEMO,
 PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A DEMO PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS. PLEASE NOTE THIS ON RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved