| Date |
Text |
| 2007-10-22 16:56:57 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA |
| | ACCESSIBILITY CODE. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. NOTE: TWO COMPLETE SETS OF THE DBPR WORK SHEETS ARE |
| | REQUIREDPER 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS, SPECIAL INSPECTION AND |
| | STRUCTURAL OBSERVATION PROGRAMS, AND |
| | OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS WITH EACH APPLICATION FOR A |
| | PERMIT. |
| | |
| | 2. SITE PLAN INDICATES AN EXISTING GREASE TRAP WITH NO |
| | SIZE BEING INDICATED. PLEASE NOTE THAT THE EXISTING |
| | GREASE TRAP WILL NEED TO BE APPROVED PER THE FOLLOWING. |
| | PER MUNICIPAL CODE ARTICLE III SECTION 90-124, |
| | THE EXISTING GREASE INTERCEPTOR SHALL BE SIZED AND |
| | LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE |
| | UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: |
| | (561) 822-2272, E-MAIL: [email protected] OR CLAVIN |
| | WILLIAMS, PHONE: (561) 822-2284, E-MAIL: |
| | [email protected]. THEIR FAX NUMBER IS (561) 822-2287. |
| | NOTE: WRITTEN APPROVAL IS REQUIRED OF THE EXISTING |
| | GREASE INTERCEPTOR FROM ENVIRONMENTAL COMPLIANCE BEFORE |
| | A PERMIT CAN BE ISSUED. |
| | |
| | 3. THE FOLLOWING HAND WRITTEN CHANGES TO THE PLANS ON |
| | SHEET A-1 H/S AND EXISTING MOP ARE UNACCEPTABLE PER |
| | CHAPTER 481, FLORIDA STATUTES, PART 1. |
| | |
| | 4. SHEET A-1 FLOOR PLAN NOTES, (4) KITCHEN IS EXISTING |
| | (ADDING EQUIPMENT UNDER EXISTING HOOD) |
| | NOTE: CLEARLY IDENTIFY WHAT EQUIPMENT IS BEING ADDED |
| | UNDER THE HOOD AND IF THE EQUIPMENT IS GAS OR ELECTRIC, |
| | PER 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 5. SHEET A-1FLOOR PLAN: IS THE NEW GRIDDLE GAS OR |
| | ELECTRIC? PLEASE CLEARLY IDENTIFY ALL APPLIANCES AND |
| | FIXTURES IN THE PROPOSED RESTAURANT WITH A LEGEND |
| | CLEARLY INDICATING IF THEY ARE GAS, ELECTRIC, NEED |
| | HOT/COLD WATER WITH PIPE SIZES, TYPE OF DRAINAGE |
| | REQUIRED GREASE/SANITARY,PER 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED |
| | |
| | 6. PER CHAPTER 1, SECTION 105THEPERMIT APPLICATION |
| | STATES "DESCRIBE PROJECT IN DETAIL (FAILURE TO DO SO |
| | MAY RESULT IN DELAYS) |
| | NOTE: THE FOLLOWING ARE NOT LISTED ON THE PERMIT |
| | APPLICATION: |
| | |
| | A} DEMO 1 EXISTING BATHROOM. |
| | |
| | B} DEMO 1 EXISTING 2 COMPARTMENT SINK. |
| | |
| | C} DEMO 1 RANGE/OVEN (UNDER EXISTING HOOD) |
| | |
| | D} DEMO PLANTERS. |
| | |
| | E} ADDING NEW GRIDDLE. |
| | |
| | F} ADDING 2 NEW FRYERS. |
| | |
| | G} ADDING 2 NEW HAND SINKS. |
| | |
| | H} ADDING 1 NEW 3 COMPARTMENT SINK (PER DBPR WORK |
| | SHEETS, NEEDS TO BE CLEARLY IDENTIFIED ON SHEET A-1). |
| | |
| | I} ADDING 1 NEW PASS THRU. |
| | |
| | J} ADDING NEW WALL AND DOOR BY SODA AND ICE MACHINE. |
| | |
| | NOTE: THE VALUE ON THE PERMIT SEEMS LOW WITH ALL THE |
| | WORK, NEW APPLIANCES AND FIXTURES BEING ADDED. PLEASE |
| | PROVIDE PROOF THAT THE ABOVE ITEMS ARE INCLUDED IN THE |
| | PERMIT VALUE WITH A COPY OF THE SIGNED CONTRACT. PLEASE |
| | PROVIDE PROOF OF FBC-2004 W/ 06 REV. SECTION |
| | 11-4.(2)(A)BEING THAT THE EXISTING BATHROOMS ARE NOT |
| | ACCESSIBLE PER FBC-2004 W/06 REV. CHAPTER 11. PER |
| | FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 7. PLEASE PROVIDE A SANITARY/GREASE AND WATER |
| | ISOMETRIC RISER DIAGRAM OF ALL NEW PROPOSED FIXTURES |
| | PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3. |
| | |
| | A} THREE COMPARTMENT SINK. |
| | B} TWO HAND SINKS. |
| | NOTE: THE HAND SINK BY THE EXISTING WALK-IN COOLER IS |
| | MISLABELED AS EXISTING. THE DEMO PLANS DO NOT INDICATE |
| | THIS SINK BY THE COOLERS. HOW CAN THIS BE EXISTING? |
| | |
| | 8. DEMO PLANS INDICATE A BATHROOM AND EXISITING 2 |
| | COMPARMENT SINK FOR DEMO, |
| | PER FBC-2004 PLUMBING, SECTION 704.5 |
| | DEAD ENDS: IN THE INSTALLATION OR |
| | REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| | A DEMO PLUMBING PERMIT REQUIRED AND |
| | INSPECTION REQUIRED OF DEMO WORK PRIOR |
| | TO COVERING DEMO WORK WITH FINNISH |
| | WALLS, CIELINGS, OR POURED CONCRETE |
| | SLABS. PLEASE NOTE THIS ON RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |