Plan Review Notes
Plan Review Notes For Permit 07080695
Permit Number 07080695
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-23 09:49:171. ENSURE THAT EXISTING EXIT SIGNS AND EMERGENCY
 LIGHTING EQUIPMENT ARE IN PROPER WORKING ORDER.
  
 2. ANY COOKING EQUIPMENT THAT IS INSTALLED UNDERNEATH
 THE HOOD SHALL TURN OFF WHEN THE HOOD EXTINGUISHING
 SYSTEM IS ACTIVATED. ALL COOKING EQUIPMENT SHALL NOT
 EXTEND BEYOND THE LIMITS OF THE KITCHEN HOOD. A MINIMUM
 OF AT LEAST 6" OF THE HOOD SHALL EXTEND BEYOND THE
 COOKING EQUIPMENT.
  
 3. OUTDOOR SEATING AREA SHALL BE PROVIDED WITH
 EMERGENCY LIGHTING EQUIPMENT.
  
 4. PORTABLE FIRE EXTINGUISHERS SHALL BE IDENTIFIED ON
 THE PLANS.
  
 5. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX