| 2007-09-15 22:04:40 | 2007-09-15 22:04:40 |
| | |
| | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE NEW DECK AREA AND EXIT EGRESS |
| | AREAS ARE REQUIRED TO MEET LIFE SAFETY CODEFOR |
| | MINIMUM LIGHT LEVELS. |
| | PLEASE SEE 7.8 AND 7.9 AND PROVIDE LIGHTING FIXTURES |
| | ALONG WITH SOME TYPE OF BATTERY BACK UP LIGHTING |
| | FIXTURE FOR THE 1FT CANDLE UNDER NORMAL AND EMERGENCY |
| | CONDITIONS. |
| | PLEASE SEE NFPA-101 2003. |
| | |
| | 2) NOTE: PLEASE SEE AS NOTE ABOVE REQUIRES NEW |
| | LIGHTING, PLEASE INDICATE CIRCUITING FOR THESE ITEMS TO |
| | PANEL(S) ALONG WITH CONDUCTOR SIZES, OVER CURRENT |
| | PROTECTION ETC. |
| | 310.16, 240.4, 408.4 |
| | |
| | 3) NOTE: PLEASE CLARIFY SERVICE ENTRANCE CONDUCTORS AS |
| | SHOWN AS AN *EQUIPMENT GROUNDING CONDUCTOR* IS BEING |
| | SHOWN AHEAD OF THE FIRST MEANS OF DISCONNECT WHICH IS |
| | NOT PERMITTED. IF THIS #4 AS SHOWN IS ACTUALLY IN |
| | PLACE, THIS IS AN UNSAFE CONDITION AND IS TO BE |
| | REMOVED. THIS CREATES OBJECTIONABLE CURRENTS PER |
| | 250.6. |
| | |
| | 250.6, 250.24. |
| | |
| | 4) NOTE: PLEASE CLARIFY SERVICE AS THE RISER INDICATES |
| | BY THE SERVICE ENTRANCE CONDUCTORS BEING A SINGLE PHASE |
| | SERVICE YET THE PANELS ARE SHOWN AS 3-PHASE?? PLEASE |
| | COORDINATE AND CORRECT AS NEEDED. |
| | 310.16, 240.4, 230.70, ETC |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE RISER AS SHOWN DOES NOT INDICATE |
| | ANY MAINS. PLEASE KNOW IF THIS IS THE INSTALLATION THE |
| | SERVICE WILL BE REQUIRED TO UP-GRADED AND CORRECTED AS |
| | THIS IS ALSO AN UN-SAFE CONDITION. |
| | BOTH PANELS ARE SHOWN AS MLO, MAIN LUG ONLY. PLEASE |
| | ALSO SEE THE SERVICE ENTRANCE CONDUCTORS AS SHOWN ARE |
| | ONLY RATED FOR 200AMPS AND ARE UN-SAFE FOR THE |
| | INSTALLATION AS SHOWN. |
| | PLEASE REVISE RISER AND INDICATE CODE COMPLIANCE. |
| | PLEASE SEE 230.70, 230.71, 230.76, 230.79, 240.4, |
| | 310.16 ETC |
| | |
| | 6) NOTE: PLEASE VERIFY IF THERE IS AN EXISTING OR NEW |
| | SIGN CIRCUIT PER 600.5. |
| | |
| | ** PLEASE KNOW AS THERE IS SEVERAL ITEMS NOT YET |
| | SUBMITTED AND SEVERAL ITEMS WHICH NEED TO BE CORRECTED |
| | A COMPLETE REVIEW FOR CODE COMPLIANCE OF SOME ITEMS CAN |
| | NOT BE DONE AT THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |