Plan Review Notes
Plan Review Notes For Permit 07080695
Permit Number 07080695
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-15 22:04:402007-09-15 22:04:40
  
 ** DENIED **
  
  
 1) NOTE: PLEASE SEE THE NEW DECK AREA AND EXIT EGRESS
 AREAS ARE REQUIRED TO MEET LIFE SAFETY CODEFOR
 MINIMUM LIGHT LEVELS.
 PLEASE SEE 7.8 AND 7.9 AND PROVIDE LIGHTING FIXTURES
 ALONG WITH SOME TYPE OF BATTERY BACK UP LIGHTING
 FIXTURE FOR THE 1FT CANDLE UNDER NORMAL AND EMERGENCY
 CONDITIONS.
 PLEASE SEE NFPA-101 2003.
  
 2) NOTE: PLEASE SEE AS NOTE ABOVE REQUIRES NEW
 LIGHTING, PLEASE INDICATE CIRCUITING FOR THESE ITEMS TO
 PANEL(S) ALONG WITH CONDUCTOR SIZES, OVER CURRENT
 PROTECTION ETC.
 310.16, 240.4, 408.4
  
 3) NOTE: PLEASE CLARIFY SERVICE ENTRANCE CONDUCTORS AS
 SHOWN AS AN *EQUIPMENT GROUNDING CONDUCTOR* IS BEING
 SHOWN AHEAD OF THE FIRST MEANS OF DISCONNECT WHICH IS
 NOT PERMITTED. IF THIS #4 AS SHOWN IS ACTUALLY IN
 PLACE, THIS IS AN UNSAFE CONDITION AND IS TO BE
 REMOVED. THIS CREATES OBJECTIONABLE CURRENTS PER
 250.6.
  
 250.6, 250.24.
  
 4) NOTE: PLEASE CLARIFY SERVICE AS THE RISER INDICATES
 BY THE SERVICE ENTRANCE CONDUCTORS BEING A SINGLE PHASE
 SERVICE YET THE PANELS ARE SHOWN AS 3-PHASE?? PLEASE
 COORDINATE AND CORRECT AS NEEDED.
 310.16, 240.4, 230.70, ETC
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE RISER AS SHOWN DOES NOT INDICATE
 ANY MAINS. PLEASE KNOW IF THIS IS THE INSTALLATION THE
 SERVICE WILL BE REQUIRED TO UP-GRADED AND CORRECTED AS
 THIS IS ALSO AN UN-SAFE CONDITION.
 BOTH PANELS ARE SHOWN AS MLO, MAIN LUG ONLY. PLEASE
 ALSO SEE THE SERVICE ENTRANCE CONDUCTORS AS SHOWN ARE
 ONLY RATED FOR 200AMPS AND ARE UN-SAFE FOR THE
 INSTALLATION AS SHOWN.
 PLEASE REVISE RISER AND INDICATE CODE COMPLIANCE.
 PLEASE SEE 230.70, 230.71, 230.76, 230.79, 240.4,
 310.16 ETC
  
 6) NOTE: PLEASE VERIFY IF THERE IS AN EXISTING OR NEW
 SIGN CIRCUIT PER 600.5.
  
 ** PLEASE KNOW AS THERE IS SEVERAL ITEMS NOT YET
 SUBMITTED AND SEVERAL ITEMS WHICH NEED TO BE CORRECTED
 A COMPLETE REVIEW FOR CODE COMPLIANCE OF SOME ITEMS CAN
 NOT BE DONE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-15 21:38:452007-09-15 21:38:45
  
 IN ELEC FOR REVIEW.