| Plan Review Notes For Permit 07080686 |
| Permit Number |
07080686 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-02 17:18:33 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | | | | 1.)OPENINGS 1 & 3 REQUIRE USE OF THE 77 ROW.THE | | | ANCHOR SPACING IS NOT COMPLIANT FOR DESIGN PRESSURE | | | DECLARED (-51.5) AS CONTRACTOR IS USING THE 47.2 ROW. | | | THIS CHART IS FOR NEGATIVE PRESSURES. | | | | | | PLEASE HAVE QUALIFIER CONTACT ME REGARDING THE DESIGN | | | PRESSURE ISSUE. | | | | | | ONE MEETING OR TELEPHONE CONVERSATION WITH THE | | | QUALIFIER WILL LIKELY GET THIS ONGOING ISSUE RESOLVED. |
|