Plan Review Notes
Plan Review Notes For Permit 07080681
Permit Number 07080681
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-14 10:48:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
  
 A. SHT P402 THE BUILDING "P" PIPING RISER DIAGRAM,
 (SANITARY), DOES NOT REFLECT THE FLOOR PLAN ON SHT
 P309. SOME BRANCH LINES MISSING AND SOME BRANCH LINES
 ARE NOT CONNECTED TO THE BUILDING DRAIN WHERE SHOWN AS
 WELL AS THE RISERS ON SOME LINES DO NOT REFLECT WHAT IS
 SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE THE
 INFORMATION ON THE RISER WITH THE INFORMATION ON THE
 FLOOR PLAN. SECTION 106.1.1.
  
 B. SHT P403 THE BUILDING "P" PIPING RISER DIAGRAM,
 (WATER), DOES NOT REFLECT THE FLOOR PLAN ON SHT P309.
 SOME BRANCH LINES MISSING AND SOME BRANCH LINES DO NOT
 CONNECT TO THE WATER MAIN LINE AS INDICATED ON THE
 FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 C. SHT P403 WATER RISERS 1W, 3W & 4WINDICATE HOT AND
 COLD WATER CONNECTING TO THE DISHWASHER. PLEASE
 CLARIFY. SECTION 106.1.2.
  
 D. THE FOLLOWING REQUIREMENTS FOR THE REQUIRED GAS
 PERMIT SHALL BE SUBMITTED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 7. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 8. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved